2015-05-04 15:25:05PERMIT # 15050015
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVISO:
  
 1) THIS PROPERTY IS EQUIPPED WITH A COMMON FIRE ALARM
 SYSTEM. AS PREVIOUSLY DISCUSSED WITH PROPERTY
 MANAGERMENT, ALL TENANT SPACES MUST HAVE PROPER
 NOTIFICATION IN THE EVENT OF A FIRE EMERGENCY. PROVIDE
 VISUAL AND AUDIBLE NOTIFICATION APPLIANCE IN ALL PUBLIC
 AND COMMON USE SPACES, AS REQUIRED BY NFPA 101: CHAPTER
 9, SECTION 9.6: FIRE DETECTION, ALARM. AND
 COMMUNICATION SYSTEMS. 9.6.3.6.1: THE GENERAL
 EVACUATION ALARM SIGNAL SHALL OPERATE THROUGHOUT THE
 ENTIRE BUILDING.
  
 2) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 COMMENTS:
  
 1) THIS PERMIT IS BEING PROVISIONALLY APPROVED PENDING
 COMPLIANCE WITH ALL ITEMS ABOVE.
  
 2) UPDATE THE CODE LIST TO REFERENCE THE 5TH EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2012 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
  
 SUE ELLEN CALDERON
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326
  