| Plan Review Notes For Permit 15050012 |
| Permit Number |
15050012 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-05-04 15:33:46 | REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW | | | COMMENTS: | | | | | | 1) INDICATE THE LOCATION IN COMPLIANCE WITH THE NEC | | | 230.70 | | | | | | 2) INDICATE THE SIZE (AMPACITY RATING) OF THE MAIN | | | OCPD, NEC 230.42 MINIMUM SIZE AND RATING. | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] | | | |
|