| Permit Number |
15041147 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-05-04 14:25:54 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | THERE IS INSUFFIECIENT DETAIL PROVIDED TO DETERMINE IF | | | THE NEWLY CREATES WALLS AFFECT THE EXISITNG FIRE | | | SPRINKLER SYSTEM AND/OR SPRINKLER HEAD PERFORMANCE. | | | PROVIDE EXISTING SPRINKLER HEAD LOCATIONS AND | | | EVALUATION NOTE STATING THE PROPOSED WORK DOES/DOES NOT | | | INTERFERE WITH EXISTING SPRINKLER HEAD PERFORMANCE. |
|