| 2015-06-09 08:06:03 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15041142 |
| | ADD: 705 N. OLIVE AVE. |
| | CONT: TBD |
| | TEL: ( 561)805-6715 |
| | E-MAIL: |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: TUES. JUNE 09/ 2015 |
| | ACTION: DENIED |
| | |
| | 1) DISCREPANCY IN ADDRESSING OF THE PROPERTY. THE |
| | PERMIT APPLICATION INDICATES THE ADDRESS TO BE 705 N. |
| | OLIVE AVE. THE PROPERTY APPRAISER HAS THIS PROPERTY'S |
| | ADDRESS AS 375 EUCALYPTUS ST, THE 3RD PHASE OF THE |
| | OVER-ALL PROJECT. PLEASE CORRECT THE PERMIT APPLICATION |
| | AND ENERGY CALCULATIONS TO REFLECT THE JOBSITE ADDRESS |
| | OF 375 EUCALYPTUS ST. PLEASE PROVIDE THE UNITITY OF |
| | TITLE. THE ADDRESS OF 705 N OLIVE DOES NOT SHOW UP WITH |
| | THE PROPERTY APPRAISERS WEB SITE WHICH IS USUAL WHEN |
| | THERE IS A REPLAT. BUT THE ADDRESS OF 375 EUCALYPTUS IS |
| | STILL SHOWING UP AS A SEPARATE PROPERTY CONTROL NUMBER |
| | AND ADDRESS. PERMIT: 14030096 : ADDRESS 705 N OLIVE IS |
| | A 8 LEVEL BUILDING, LOFTIN PLACE, A DIFFERENT LOCATION, |
| | PCN NUMBER AND ADDRESS. |
| | |
| | 2) 2ND REQUEST. I'VE SPOKE WITH THE BUILDING OFFICIAL |
| | R. BROWN ABOUT THIS ISSUE, AND HE DOES NOT WANT TO HAVE |
| | A NEW ELEMENT BE A CODE VILATION. |
| | SHEET A.0 TEMPORARY LEASING OFFICE DOES NOT SHOW WHERE |
| | THE PROPERTY LINE IS LOCATED, IT CAN NOT BE DETERMINED |
| | IF THE FRONT ENTRY DOOR CROSSES OVER THE PROPERTY LINE. |
| | PLEASE SHOW COMPLIANCE WITH 2010 FBC-B 3202.2 |
| | ENCROACHMENTS ABOVE GRADE AND BELOW 8 FEET IN HEIGHT. |
| | DOORS AND WINDOWS SHALL NOT OPEN OR PROJECT INTO THE |
| | PUBLIC RIGHT-OF-WAY. |
| | |
| | 3) BUILDING PROVISO: |
| | THIS ONE ISSUE WILL BE RULED ON BY THE FIRE DEPARTMENT |
| | AND SINCE THEY WERE THE ONES THAT APPROVED THE LOCATION |
| | OF THE CONSTRUCTION TRAILER WITH THE STIPULATION THAT |
| | THE BUILDING WOULD BE LEFT UN-OCCUPIED. SHEET A.0 |
| | INDICATES TO THE EAST A CLEAR DRIVEWAY OF 20 FT. PLEASE |
| | BE AWARE THE CONSTRUCTION TRAILERS ARE JUST TO THE EAST |
| | OF THE DRIVEWAY. ONE OF THE CONDITIONS THAT THE FIRE |
| | DEPARTMENT PUT ON THE PLACEMENT OF THE CONSTRUCTION |
| | TRAILERS WAS COMPLIANCE WITH NFPA 251 WITH 60 FEET OF |
| | EXPOSED SIDE O FTHE TRAILER THEY WOULD BE REQUIRED TO |
| | BE 50 FEET AWAY FROM BUILDINGS. AN AGREEMENT WAAS MET |
| | THAT KAST COULD LEAVE THEIR CONSTRUCTION TRAILER WHERE |
| | IT WAS IF THE BUILDING TO THE WEST WAS LEFT UNOCCUPIED. |
| | NOW IT WOULD APPEAR THAT EITHER THE BUILDING REMAIN |
| | UNOCCUPIED OR KAST CONSTRUCTION TRAILER BE MOVED EAST |
| | TO COMPLY WITH NFPA 251. |
| | |
| | 4) COMPLIED. SHEETS A1 & A2 BOTH SHOW THE EXISTING |
| | WINDOWS TO BE BLOCKED IN, THERE IS NO INFORMATION AS TO |
| | HOW THE NEW INFILL WILL BE TIED TO THE EXISTING |
| | BLOCKWORK. |
| | 2010 FBC-B 2104.1.3 INSTALLATION OF WALL TIES. WALL |
| | TIES SHALL BE INSTALLED IN ACCORDANCE WITH TMS 602/ACI |
| | 530.1/ASCE 6. |
| | |
| | 5) 2ND REQUEST. SHEET A2 INDICATES VASD PRESSURES FOR |
| | THE NEW OPENING. THE PLANS FAIL TO IDENTFY THE |
| | WINDDESIGN CRITERIA, THE IMPORTANCE FACTOR OF THE |
| | BUILDING, EXPOSURE CATEGORY OF THE BUILDING AND OR IF |
| | HEIGHT ADJUSTMENT FACTORS ARE INVOLVED. THESE LISTED |
| | CRITERIA DETERMINES THE PRESSURES, WITHOUT THIS |
| | INFORMATION, WE CAN'T DETERMINE WHAT CRITERIA THE |
| | DESIGNER OF RECORD ARRIVED THE PRESSURES FOR THE |
| | OPENING. |
| | |
| | BOTH SHEETS A1 & A2 BOTH INDICATE A NEW WIDER FRONT |
| | ENTRY DOOR PLEASE PROVIDE THE WIND DESIGN CRETERIA; |
| | WIND DESIGN CRITERIA |
| | 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- |
| | CHAPTER 6 OF ASCE 7-10. |
| | 1609.3 BASIC WIND SPEED FIGURE 1609.A-C |
| | 1609.3 WIND SPEED CONVERSION |
| | |
| | 5.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.3.1 & ASCE 7-10 |
| | |
| | 5.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10. |
| | |
| | 5.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.4 & ASCE 7-10 |
| | |
| | 5.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| | SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. |
| | |
| | 5.5) COMPONENTS & CLADDING PRESSURES POSITIVE & |
| | NEGATIVE TABLE 1609.2(2) . |
| | |
| | 6) COMPONENTS & CLADDING 2010 FBC-B 1609.1.2 PROTECTION |
| | OF OPENINGS, 1609.6.4.41 COMPONENTS & CLADDING. FLORIDA |
| | DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 |
| | (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS |
| | THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS |
| | (B) WINDOW |
| | (C) MULLION |
| | 7) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 7A) ONCE THEWIND DESIGN CRITERIA & PRESSURES ARE |
| | REVIEWED AND APPROVED. EITHER THE DESIGNER OF RECORD OR |
| | THE CONTRACTOR CAN ELECT TO SUBMIT THE PRODUCT |
| | APPROVALS AFTER THE PERMIT ISSUANCE, WRITTEN |
| | NOTIFICATION IS REQUIRED. |
| | |
| | 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS |
| | SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR |
| | DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE |
| | REGISTERED DESIGN |
| | PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL REVIEW |
| | THEM AND FORWARD THEM TO THE BUILDING OFFICIAL WITH A |
| | NOTATION INDICATING THAT THE DEFERRED SUBMITTAL |
| | DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL |
| | CONFORMANCE TO THE DESIGN OF THE BUILDING. THE DEFERRED |
| | SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE |
| | DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE |
| | BUILDING OFFICIAL. |
| | |
| | |
| | 8-13) COMPLIED. |
| | |