Plan Review Notes
Plan Review Notes For Permit 15041132
Permit Number 15041132
Review Stop E
Sequence Number 2
Notes
Date Text
2015-07-21 14:05:00APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN APPROVED
 PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION
 FEE(S).
  
 1) 505.2 LIGHTING CONTROLS (MANDATORY).
 LIGHTING SYSTEMS SHALL BE PROVIDED WITH CONTROLS AS
 REQUIRED IN SECTIONS 505.2.1, 505.2.2, 505.2.3 AND
 505.2.4.
  
 2) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR FIRE ALARM, ACCESS CONTROL SYSTEM,
 SECURITY, CCTV, AUDIO/VIDEO, NETWORK, DATA, AND,
 COMMUNICATION AND POS SYSTEMS AS NEEDED.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  