| Plan Review Notes For Permit 15041132 |
| Permit Number |
15041132 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-06-03 15:09:59 | NO ELECTRICAL PLAN HAS BEEN INCLUDED IN THE SUBMITTAL | | | PACKAGE. NO ELECTRICAL REVIEW HAS BEEN PERFORMED AT | | | THIS TIME. | | | | | | 1) PROVIDE AN ELECTRICAL PLAN FOR REVIEW THAT INCLUDES | | | THE MINIMUM PLAN REVIEW CRITERIA. | | | | | | WPB AMENDMENTS TO THE FBC 107.3.5.1.2 MINIMUM PLAN | | | REVIEW FOR ELECTRICAL: | | | 1. A SERVICE RISER DIAGRAM | | | 2. INDICATE ALL FEEDERS AND BRANCH CIRCUITS | | | 3. PROVIDE A PANEL SCHEDULE WITH OVERCURRENT PROTECTION | | | AND CORRESPONDING WIRE SIZES. | | | 4. GROUNDING AND BONDING. | | | 5. WIRING METHODS AND MATERIALS | | | 6. GFCI PROTECTION WHERE REQUIRED. | | | 7. AN EQUIPMENT SCHEDULE | | | 8. GENERAL LIGHTING | | | 9. EMERGENCY AND EXIT LIGHTING | | | | | | | | | |
|