2015-06-03 15:09:59NO ELECTRICAL PLAN HAS BEEN INCLUDED IN THE SUBMITTAL
 PACKAGE. NO ELECTRICAL REVIEW HAS BEEN PERFORMED AT
 THIS TIME.
  
 1) PROVIDE AN ELECTRICAL PLAN FOR REVIEW THAT INCLUDES
 THE MINIMUM PLAN REVIEW CRITERIA.
  
 WPB AMENDMENTS TO THE FBC 107.3.5.1.2 MINIMUM PLAN
 REVIEW FOR ELECTRICAL:
 1. A SERVICE RISER DIAGRAM
 2. INDICATE ALL FEEDERS AND BRANCH CIRCUITS
 3. PROVIDE A PANEL SCHEDULE WITH OVERCURRENT PROTECTION
 AND CORRESPONDING WIRE SIZES.
 4. GROUNDING AND BONDING.
 5. WIRING METHODS AND MATERIALS
 6. GFCI PROTECTION WHERE REQUIRED.
 7. AN EQUIPMENT SCHEDULE
 8. GENERAL LIGHTING
 9. EMERGENCY AND EXIT LIGHTING
  
  
  