| 2015-06-15 10:51:23 | 1ST REVIEW: FBC 2010 MECHANICAL |
| | |
| | 1) SUBMIT MANUFACTURER'S SPECIFICATIONS (CUT SHEETS) |
| | FOR THE SPRAY BOOTH, FANS, AND SPRAY EQUIPMENT- |
| | SECTIONS 5.1, 7.10, AND 11.1 NFPA 33. THE EXHAUST FANS |
| | SHALL BE IN COMPLIANCE WITH SECTION 502.7.3.6 FBC- |
| | MECHANICAL: FANS NOT PERMITTED IN DUCTS, AND SHALL HAVE |
| | NON-FERROUS OR NON-SPARKING ROTATING ELEMENTS. |
| | 2) THE PLAN INDICATES NON-COMPLIANCE FOR THE REQUIRED |
| | 3' CLEARANCE TO BE MAINTAINED ON ALL SIDES OF THE BOOTH |
| | SECTION 5.3.2 NFPA 33. RELOCATE THE BOOTH OR PROVIDE |
| | DATA CONSISTENT WITH EXCEPTIONS 1 OR 2. |
| | 3) PROVIDE CALCULATIONS FOR THE VENTILATION SYSTEM |
| | INDICATING COMPLIANCE WITH THE 100 CFM AIR VELOCITY |
| | REQUIREMENT PER SECTION 502.7.3.3 FBC-10 MECHANICAL. |
| | 4) INDICATE A SEQUENCE OF OPERATIONS INDICATING HOW |
| | CONTINUOUS VENTILATION WILLL BE PROVIDED DURING SPRAY |
| | OPERATIONS- SECTION 502.7.3.1 MECHANICAL. |
| | 5) PROVIDE A DETAIL SHOWING THE EXHAUST DISHARGE |
| | HEIGHTS ABOVE THE ROOF IN COMPLIANCE WITH SECTION 7.4 |
| | NFPA- 33: MINIMUM 6 FT. ABOVE THE ROOF SURFACE. |
| | 6) PROVIDE A ROOF PLAN INDICATING THE CLEARANCE |
| | DISTANCE MEASUREMENTS OF THE EXHAUST DISCHARGE TO THE |
| | PROPERTY LINE, THE AIR INTAKE AND OTHER OPERABLE |
| | OPENINGS, AND EXTERIOR WALLS AND ROOFS- 501.2.1(1). |
| | 7) SHOW A MEANS OF SUPPORT FOR THE DUCTS ABOVE AND |
| | BELLOW THE ROOF- SECTION 7.8 NFPA 33. PLEASE NOTE THAT |
| | EQUIPMENT INSTALLED ABOVE THE ROOF SHALL BE ANCHORED TO |
| | WITHSTAND 170 MPH WIND LOADS. |
| | 8) IDENTIFY AND LABEL THE STORAGE MIXING AREAS ON THE |
| | PLAN, AND INDICATE THE QUANTITIES OF FLAMMABLE AND |
| | COMBUSTIBLE LIQUIDS TO BE STORED AND HANDLED IN THESE |
| | ROOMS OR SPACES, AND HOW THEY WILL BE VENTILATED- SEE |
| | CHAPTER 8 NFPA 33, AND SECTION 502.8 FBC-10 MECHANICAL. |
| | 9) PROVIDE COMPLETE PLANS, DETAILS, AND SPECIFICATIONS |
| | FOR THE REQUIRED AUTOMATIC FIRE PROTECTION SYSTEM- |
| | SECTION 9.1 NFPA 33; OR INDICATE ON THE PLAN IT WILL BE |
| | DONE UNDER SEPARATE PERMIT. |
| | |