| | PROJECT: RELIEF AUTO BODY |
| | PERMIT#: 15041121 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW |
| | COMMENTS: |
| | |
| | 1) NEC 220. |
| | PROVIDE A TOTAL CONNECTED LOAD SUMMARY CALCULATION |
| | INDICATING THE ADDITIONAL LOAD OF THE NEW SPRAY BOOTH |
| | EQUIPMENT. |
| | |
| | 2) NEC 230.42(B) |
| | THE SERVICE ENTRANCE INDICATED ON THE RISER DIAGRAM HAS |
| | BEEN UNDERSIZED. THE MINIMUM AMPACITY FOR UNGROUNDED |
| | CONDUCTORS FOR SPECIFIC INSTALLATIONS SHALL NOT BE LESS |
| | THAN THE RATING OF THE SERVICE DISCONNECTING MEANS. |
| | |
| | 3) NEC 310.16 |
| | USE THE NEC 310.16 TO SIZE THE SERVICE ENTRANCE |
| | CONDUCTORS. |
| | |
| | 4) NEC 210.19(A) |
| | THERE ARE CIRCUITS IN THE PANEL SCHEDULE WITH |
| | UNDERSIZED CONDUCTORS CONNECTED TO OCPD. BRANCH-CIRCUIT |
| | CONDUCTORS SHALL HAVE AN AMPACITY NOT LESS THAN THE |
| | MAXIMUM LOAD TO BE SERVED. NEC 210.19(A) |
| | |
| | 5) NEC 408.4 |
| | EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY |
| | IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND SPECIFIC |
| | PURPOSE OR USE. NEC 408.4 |
| | |
| | 6) WPB AMENDMENTS TO THE FBC 107.2.5 |
| | INDICATE THE LOCATION OF THE ELECTRICAL SERVICE ON THE |
| | BUILDING RELATIVE TO THE LOCATION OF THE NEW SPRAY |
| | BOOTH. |
| | |
| | 7) WPB AMENDMENTS TO THE FBC 107.2.5 |
| | INDICATE THE LOACTION OF THE ELECTRICAL PANEL ON OR IN |
| | THE BUILING RELATIVE TO THE LOCATION OF THE NEW SPRAY |
| | BOOTH. |
| | |
| | 8) WPB AMENDMENTS TO THE FBC 107.3.5.1.2 |
| | INDICATE THE LOCATION ON A FLOOR PLAN OF THE SWITCHES, |
| | OUTLETS, LIGHTS, FANS, MOTORS, CONTROLERS, DISCONNECTS, |
| | ETC ON, IN, ON, AND/OR AROUND THE SPRAY BOOTH. INDICATE |
| | WHICH ARE NEW AND WHICH ARE EXISTING TO REMAIN. |
| | |
| | 9) NEC 516.3 |
| | INDICATE THE HAZARDOUS LOCATIONS ON THE FLOOR PLAN AND |
| | INDICATE WHICH OF THE DEVICES WITHIN THOSE LOCATIONS |
| | ARE TO BE HOUSED AND OR PROTECTED BY EQUIPMENT SUITABLE |
| | FOR THAT ENVIRONMENT. |
| | |
| | 10) NEC 516 |
| | PROVIDE MANUFACTURER PRODUCT APPROVAL DOCUMENTS |
| | INDICATING COMPLIANCE WITH THE NEC 110(3)(B) AND NEC |
| | 516. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |