Plan Review Notes
Plan Review Notes For Permit 15041105
Permit Number 15041105
Review Stop E
Sequence Number 1
Notes
Date Text
2015-05-01 10:59:50NO ELECTRICAL PLAN HAS BEEN INCLUDED IN THE SUBMITTAL
 PACKAGE. NO ELECTRICAL REVIEW HAS BEEN PERFORMED AT
 THIS TIME. AN ELECTRICAL PERMIT IS REQUIRED FOR AN
 ELECTRICAL CONTRACTOR TO COMPLETE THE ELECTRICAL WIRING
 REQUIRED FOR THE IGNITER CIRCUIT IN GAS APPLIANCES.
  
 1) PROVIDE AN ELECTRICAL PERMIT APPLICATION WITH A
 FLOOR PLAN AND A PANEL SCHEDULE INDICATING THE
 ELECTRICAL CIRCUITS AND DISCONNECTS REQUIRED FOR THE
 NEW GAS APPLIANCES WITH ELECTRONIC IGNITER CIRCUITS.
 NEC 422.31
  
 2) PROVIDE ADDITIONAL INFORMATION ON THE FLOOR PLAN AND
 PANEL SCHEDULE THAT INDICATE THE DEMOLITION OF THE
 ASSUMED PREVIOUSLY EXISTING STORAGE WATER HEATER. WPB
 AMENDMENTS TO THE FBC 107.3.2
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]