| Plan Review Notes For Permit 15041103 |
| Permit Number |
15041103 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-05-02 11:21:08 | !) SUBMIT A CLEAR AND DESCRIPTIVE NARRATIVE AS TO THE | | | ENTIRE SCOPE OF WORK TO BE DONE. FROM THE SUBMITTED | | | DRAWING I CANNOT DETERMINE WHAT TYPE OF WORK IS BEING | | | DONE ON THE EXTERIOR UNDERGROUND PLUMBING LINES. THERE | | | IS NO DESCRIPTION OF THIS WORK ON THE APPLICATION.WPB | | | AMENDMENTS TO 2010 FPC SEC.107.2.1. | | | 2) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR THE | | | TANKLESS WATER HEATER. THE DOCUMENT THAT WAS SUBMITTED | | | IS INADEQUATE. | | | 3) WHAT IS BEING DONE WITH THE PLUMBING ON THE EXTERIOR | | | KITCHEN WALL? THE PLAN IS UNCLEAR AND CONFUSING.WPB | | | AMEND. TO 2010 FBC SEC. 107.2.1. | | | 4) INDICATE ON THE PLAN IF THE TANKLESS WATER HEATER IS | | | REPLACING AN EXISTING TANKLESS WATER HEATER OR | | | REPLACING A TANK TYPE WATER HEATER. | | | 5) AN ELECTRIC PLAN, APPLICATION, AND PERMIT MAY BE | | | REQUIRED FOR THE SCOPE OF WORK BEING DONE.WPB AMEND. TO | | | 2010 FBC SEC. 105.1. | | | 6) SUBMIT A CLEAR AND LEGIBLE PLUMBING PLAN FOR REVIEW. | | | WPB AMEND. TO 2010 FBC SEC. 107.2.1. | | | 7) WILL ANY OF THE WALL BE REMOVED AND REPLACED TO | | | REPLACE THE TUB/SHOWER VALVE? IF SO, A SEPARATE PERMIT | | | MAY BE REQUIRED, | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|