| 2015-05-04 06:30:26 | 1) INDICATE ON THE PLANS IF THE EXISTING TILE AND |
| | SUBSTRATE OF THE WALLS SURROUNDING THE EXISTING TUB |
| | WILL BE COMPLETELY REMOVED AND REPLACED. IF NOT, SHOW |
| | THE EXTENT OF THE AREA TO BE REPLACED/REPAIRED. WPB |
| | AMEND. TO 2010 FBC SEC. 107.2.1. |
| | 2) IF THE WALL SUBSTRATE IS GOING TO BE REPLACED, THE |
| | SUBSTRATE SHALL COMPLY WITH 2010 FBC SEC.2509.3.WATER |
| | RESISTANT GYPSUM BACKING BOARD SHALL NOT BE USED IN |
| | AREAS LISTED IN FBC 2509.3. INDICATE SO ON THE PLANS. |
| | 3) INDICATE ON THE PLANS IF ANY OF THE FLOOR TILE WILL |
| | BE REPLACED. IF SO, SUBMIT MANUFACTURER'S PRODUCT |
| | SHEETS FOR THE UNDERLAYMENT FOR THE TILE. SEE 2010 FBC |
| | SEC.1207.3 FOR STRUCTURE-BORNE SOUND REQUIREMENTS. |
| | 4) INDICATE ON THE PLAN IF ANY OF THE WALLS OF THE TUB |
| | IS A TENANT SEPARATION WALL. IF SO, COMPLIANCE WITH |
| | 2010 FBC SEC.1207.2 SHALL BE MET FOR AIR-BORNE SOUND. |
| | 5) IF THE FLOOR TILE IS BEING REPLACED, THE SOUND |
| | INSULATION MATERIAL SHALL COMPLY WITH 2010 FBC SEC. |
| | 603.1 (2). SEE EXCEPTION #2. |
| | 6) IF THE TYPE OF CONSTRUCTION OF THE BUILDING IS TYPE |
| | I OR TYPE II THE SOUND INSULATION SHALL COMPLY WITH |
| | 2010 FBC SEC.703.4 FOR NONCOMBUSTIBILITY. SEE ALSO FBC |
| | SECS.703.4.1 & 703.4.2. INDICATE THE TYPE OF |
| | CONSTRUCTION ON THE PLANS. |
| | 7) INDICATE ON THE PLANS IF ANY OF THE TUB WALLS ARE |
| | FIRE RATED WALLS. IF SO, INDICATE THE FIRE RATING OF |
| | SUCH WALL AND A LISTED RATED WALL ASSEMBLY DETAIL FOR |
| | THE REPAIR/REPLACEMENT OF THE WALL SUBSTRATE. |
| | 8) ANY BACKING IN THE WALLS THAT MAY HAVE BEEN THERE |
| | FOR THE FUTURE INSTALLATION OF GRAB BARS FOR FAIR |
| | HOUSING REQS.SHALL BE REPLACED WITH LIKE MATERIAL (IF |
| | APPLICABLE). WOOD SHALL BE FIRE RETARDANT TREATED WOOD |
| | PER FBC 2010 CHAPT.6. |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | 561-805-6692 |
| | [email protected] |
| | |