| Plan Review Notes For Permit 15041080 |
| Permit Number |
15041080 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-04-29 16:57:28 | THE REVIEW COMMENTS BELOW ARE NO LONGER A CONCERN FOR | | | THIS PERMIT. THE ELECTRICAL SCOPE OF THE PERMIT HAS | | | BEEN ADDRESSED BY ELECTRICAL PERMIT #15040877 AND THE | | | REVISION TO THAT PERMIT, REVISION#15041053 WHCH COVERS | | | THE ELECTRICAL SCOPE OF WORK ADRESSED BELOW. | | | | | | 1) PROVIDE FLOOR PLANS INDICATING FULL SCOPE OF | | | ELECTRICAL WORK. | | | | | | 2) PROVIDE PANEL SCHEDULE INDICATING ANY NEW CIRCUITS. | | | EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY | | | IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND SPECIFIC | | | PURPOSE OR USE. NEC 408.4 | | | | | | 3) INDICATE LOCATIONS OF REQUIRED SMOKE DETECTORS. WHEN | | | ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A PERMIT | | | OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE ADDED OR | | | CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL DWELLING | | | UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS LOCATED AS | | | REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL 314 AND | | | 315. | | | | | | 4) INDICATE REQUIRED CIRCUITS ON FLOOR PLAN. NEC 210.52 | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] |
|