Plan Review Notes
Plan Review Notes For Permit 15041080
Permit Number 15041080
Review Stop E
Sequence Number 1
Notes
Date Text
2015-04-29 16:57:28THE REVIEW COMMENTS BELOW ARE NO LONGER A CONCERN FOR
 THIS PERMIT. THE ELECTRICAL SCOPE OF THE PERMIT HAS
 BEEN ADDRESSED BY ELECTRICAL PERMIT #15040877 AND THE
 REVISION TO THAT PERMIT, REVISION#15041053 WHCH COVERS
 THE ELECTRICAL SCOPE OF WORK ADRESSED BELOW.
  
 1) PROVIDE FLOOR PLANS INDICATING FULL SCOPE OF
 ELECTRICAL WORK.
  
 2) PROVIDE PANEL SCHEDULE INDICATING ANY NEW CIRCUITS.
 EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY
 IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND SPECIFIC
 PURPOSE OR USE. NEC 408.4
  
 3) INDICATE LOCATIONS OF REQUIRED SMOKE DETECTORS. WHEN
 ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A PERMIT
 OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE ADDED OR
 CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL DWELLING
 UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS LOCATED AS
 REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL 314 AND
 315.
  
 4) INDICATE REQUIRED CIRCUITS ON FLOOR PLAN. NEC 210.52
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]