| 2015-05-27 09:04:11 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15041067 |
| | ADD: 529 S. FLAGLER DR. SUITE # 28-H |
| | CONT: CAMBRIDGE CONSTRUCTION |
| | TEL: (561)784-3722 |
| | E-MAIL:[email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: WED. MAY 27/2015 |
| | ACTION: DENIED |
| | |
| | NOTICE: CHAPTER 553.80(2)(B) FLORIDA STATUTES STATES |
| | THAT A LOCAL GOVERNMENT SHALL IMPOSE A FEE OF FOUR |
| | TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE REJECTED |
| | (3) OR MORE TIMES FOR REPEATED FAILURE TO CORRECT A |
| | CODE VIOLATION. |
| | |
| | 1) 2ND REQUEST. DESIGN FOR WIND BY RAYOMND CHLADNY |
| | ARCHITECT, NOTE THE DESIGNER OF RECORD SEALED THE PLANS |
| | WITH HIS AA CERTIFICATE OF AUTHORITY SEAL. 61 G |
| | 1-16.003 USES OF SEAL. EFFECTIVE 04/18/2000 THE |
| | PERSONAL SEAL, SIGNATURE AND DATE OF THE ARCHITECT OR |
| | INTERIOR DESIGNER SHALL APPEAR ON ALL ARCHITECTURAL OR |
| | INTERIOR DESIGN DOCUMENTS TO BE FILED FOR PUBLIC RECORD |
| | AND SHALL BE CONSTRUED TO OBLIGATE HIS PARTNERS OR HIS |
| | CORPORATION. A CORPORATE SEAL ALONE IS INSUFFICIENT. |
| | DOCUMENTS SHALL BE SIGNED PERSONALLY AND SEALED BY THE |
| | RESPONSIBLE ARCHITECT |
| | |
| | 2) 2ND REQUEST. NOTICE!!!!!!!!!!! PLEASE NOTE THE WIND |
| | DESIGN CRITERIA WAS PROVIDED, WHAT WAS NOT PROVIDED WAS |
| | THE SIZE OF THE WINDOWS AND DOORS NOR WHERE ZONE 4 AND |
| | 5 START AND END. THE PRESSUES NEED TO ALIGN WITH THE |
| | SIZE OF OPENING AND ZONE EITHER 4 OR 5. EITHER THE |
| | ARCHITECT OR CONTRACTOR IS TO PROVIDE THE SIZES OF THE |
| | OPENINGS, TYPE OF GLAZING, SILL HEIGHT OF THE SLIDING |
| | DOORS TO BE INSTALLED, CIRCLE TO IDENTIFY AND |
| | ASSOCIATED PRESSURES. ON THE SUBMITTED PLANS THE |
| | ARCHITECT HAS STATED THAT THE MOST SEVERVE WIND |
| | PRESSURE COMES TO -98.45 PSF PLEASE PROVIDE THE SIZE OF |
| | THIS OPENING, IT APPEARS TO BE LOW. |
| | |
| | 3) 2ND REQUEST . 2010 FBC 107.3.4.1 PRODUCT APPROVALS. |
| | THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE |
| | 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 4) 2ND REQUEST. SUBMITTED SUPERSAM 125 HAS A IIC RATING |
| | OF 49. PLEASE PROVIDE TESTING FOR CODE COMPLIANCE FOR |
| | FLOOR INSULATION: BLDG TYPE: TYPE I/ TYPE II FLOOR |
| | INSULATION |
| | |
| | 4A) THE DESIGNER OF RECORD TO VERIFY THE SLAB THICKNESS |
| | FOR THIS BUILDING. THE SUBMITTED TESTING REPORT ASTM |
| | E-492 FOR PROFLEX MSC 90 WITH A IMPACT INSULATION CLASS |
| | IIC OF 68 DB IS WITH A SUSPENDED CEILING OF 5/8 INCH |
| | TYPE X DRYWALL ATTACHED TO A SUSPENDED RIGID X CEILING |
| | FRAME AND 3 1/2INCHES OF INSULATION. THE TEST HAS TO BE |
| | WITH THE TILE, THIN SET, SOUND UNDERLAYMENT AND |
| | ADHESIVE AND CONCRETE SLAB. |
| | |
| | FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND. FLOOR/CEILING |
| | ASSEMBLIES BETWEEN DWELLING UNITS OR BETWEEN A DWELLING |
| | UNIT AND A PUBLIC OR SERVICE AREA WITHIN THE STRUCTURE |
| | SHALL HAVE AN IMPACT INSULATION CLASS (IIC) RATING OF |
| | NOT LESS THAN 50 (45 IF FIELD TESTED) WHEN TESTED IN |
| | ACCORDANCE WITH ASTM E 492. |
| | |
| | 4B) THE SUBMITTED TESTING REPORT ASTM E-90 FOR PROFLEX |
| | MSC 90 WITH ASOUND TRANSMISSION CLASS OF STC= 72 DB FOR |
| | PROFLEX MSC 90 IS WITH A SUSPENDED CEILING OF 5/8 INCH |
| | TYPE X DRYWALL ATTACHED TO A SUSPENDED RIGID X CEILING |
| | FRAME AND 3 1/2INCHES OF INSULATION. THE TEST HAS TO BE |
| | WITH THE TILE, THIN SET, SOUND UNDERLAYMENT AND |
| | ADHESIVE AND CONCRETE SLAB. |
| | |
| | FBC-B 2010 1207.2 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | 5) COMPLIED. FLAME SPREAD- FBC-B 2010 603.1.2 EXCEPTION |
| | 2. INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND |
| | SOLID DECKING WITHOUT INTERVENING AIRSPACE SHALL BE |
| | ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN |
| | 200. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 703.4 NONCOMBUSTIBILITY TESTS. |
| | THE TESTS INDICATED IN SECTIONS 703.4.1 AND 703.4.2 |
| | SHALL SERVE AS CRITERIA FOR ACCEPTANCE OF BUILDING |
| | MATERIALS AS SET FORTH IN SECTIONS 602.2, 602.3 AND |
| | 602.4 IN TYPE I, II, III AND IV CONSTRUCTION. THE TERM |
| | ?NONCOMBUSTIBLE? DOES NOT APPLY TO THE FLAME SPREAD |
| | CHARACTERISTICS OF INTERIOR FINISH OR TRIM MATERIALS. A |
| | MATERIAL SHALL NOT BE CLASSIFIED AS A NONCOMBUSTIBLE |
| | BUILDING CONSTRUCTION MATERIAL IF IT IS SUBJECT TO AN |
| | INCREASE IN COMBUSTIBILITY OR FLAME SPREAD BEYOND THE |
| | LIMITATIONS HEREIN ESTABLISHED THROUGH THE EFFECTS OF |
| | AGE, MOISTURE OR OTHER ATMOSPHERIC CONDITIONS. |
| | |
| | 703.4.1 ELEMENTARY MATERIALS. |
| | MATERIALS REQUIRED TO BE NONCOMBUSTIBLE SHALL BE TESTED |
| | IN ACCORDANCE WITH ASTM E 136. |
| | |
| | 703.4.2 COMPOSITE MATERIALS. |
| | MATERIALS HAVING A STRUCTURAL BASE OF NONCOMBUSTIBLE |
| | MATERIAL AS DETERMINED IN ACCORDANCE WITH SECTION |
| | 703.4.1 WITH A SURFACING NOT MORE THAN 0.125 INCH (3.18 |
| | MM) THICK THAT HAS A FLAME SPREAD INDEX NOT GREATER |
| | THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84 OR UL |
| | 723 SHALL BE ACCEPTABLE AS |
| | NONCOMBUSTIBLE MATERIALS. |
| | |
| | 6) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 107.3.5 |
| | MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. THE |
| | EXAMINATION OF THE DOCUMENTS BY THE BUILDING OFFICIAL |
| | SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA AND |
| | DOCUMENTS: A FLOOR PLAN. |
| | |
| | 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |