| 2015-06-23 09:47:53 | 6/23/2015 |
| | PROJECT: GLUE PRODUCTS |
| | PERMIT#: 15041010 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC, |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 2ND ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | BELOW IS THE LIST OF ITEMS REQUESTED ON THE FIRST |
| | REVIEW ALONG WITH THE ITEMS PROVIDED ON YOUR |
| | RE-SUBMITTAL. AS NOTED, THERE IS A DEFICIENCY AND NOT |
| | UNTIL ALL ITEMS ARE PROVIDED WILL THIS PERMIT BE |
| | APPROVED. THE RISER DIAGRAM YOU PROVIDED DOES NOT MATCH |
| | THE ONE ON THE PLANS. IF THE ONE ON THE PLANS IS |
| | INCORRECT, PLEASE CROSS IT OUT. PER NEC REQUIREMENTS |
| | YOU SHALL PROVIDE A LOAD CALC OF THE4 EXISTING TO |
| | ASCERTAIN THAT THE SERVICE WILL ABSORB THE ADDED LOAD |
| | PROPERLY. |
| | |
| | |
| | MISSING 1. PROVIDE THE CIRCUITRY ON THE FLOOR PLAN TO |
| | COINCIDE WITH THE REQUIRED PANEL SCHEDULE AS WELL AS A |
| | RISER DIAGRAM AND LOAD CALCULATION. FBC 107.3.5 |
| | ELECTRICAL |
| | |
| | MISSING 2. PROVIDE COMPLETE CIRCUIT DIRECTORIES FOR |
| | ELECTRICAL PANELS. EVERY CIRCUIT SHALL BE LEGIBLY |
| | IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND SPECIFIC |
| | PURPOSE OR USE. NEC 408.4 |
| | |
| | MISSING 3. INDICATE THE REQUIRED LIGHTING CONTROLS FOR |
| | INTERIOR AND EXTERIOR ILLUMINATION. LIGHTING SYSTEMS |
| | SHALL BE PROVIDED WITH CONTROLS AS REQUIRED IN |
| | FBC-ENERGY CONSERVATION SECTIONS 505 ELECTRICAL POWER & |
| | LIGHTING SYSTEMS (MANDATORY). |
| | |
| | MISSING 4. INDICATE THE REQUIRED LIGHTING ABOUT |
| | ELECTRICAL EQUIPMENT. ILLUMINATION SHALL BE PROVIDED |
| | FOR ALL WORKING SPACES ABOUT ELECTRICAL PANELS AND |
| | EQUIPMENT. NEC 110.26 (D) |
| | |
| | MISSING 5. VERIFY SAFETY LABELING FOR ARC FLASH |
| | PROTECTION FOR THE PANEL BOARDS AND MAIN DISCONNECTING |
| | MEANS. NEC 110.16 |
| | |
| | MISSING 6. INDICATE ALL REQUIRED EMERGENCY |
| | ILLUMINATION. EMERGENCY ILLUMINATION SHALL INCLUDE ALL |
| | REQUIRED MEANS OF EGRESS LIGHTING, ILLUMINATED EXIT |
| | SIGNS, AND ALL OTHER LIGHTS SPECIFIED AS NECESSARY TO |
| | PROVIDE REQUIRED ILLUMINATION. NEC 700.16(F) |
| | |
| | INCOMPLETE 7. PROVIDE THE LOCATION OF ALL MECHANICAL |
| | EQUIPMENT WITH ASSOCIATED REQUIRED DISCONNECTS AND GFI |
| | OUTLETS. NEC 210.63, 210.8(A)(3), NEC 440.14, THE FIRE |
| | PLAN DOES HAVE AN INDICATION OF THE LOCATION, BUT IT |
| | DOES NOT COMPLY WITH THE ELECTRICAL REQUIREMENTS. |
| | |
| | MAY NOT BE NECESSARY AS ONLY THE MIX ROOMS ARE BEING |
| | ADDED TO THE EXISTING LOCATION 8. INDICATE PROVISIONS |
| | FOR THE REQUIRED SIGN CIRCUIT AND SHOW WINDOW LIGHTING. |
| | NEC 210.62, 600.5(A) |
| | |
| | COMPLETE (15060821) 9. SEPARATE ELECTRICAL PERMIT |
| | ACCOMPANIED BY MANUFACTURER?S EQUIPMENT SUBMITTAL |
| | REQUIRED, FOR ELECTRICAL WORK |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | |
| | MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353, |
| | 561-805-7943 OR [email protected] |
| | |
| | |