Plan Review Notes
Plan Review Notes For Permit 15041010
Permit Number 15041010
Review Stop M
Sequence Number 1
Notes
Date Text
2015-05-07 15:28:27PLAN DENIED
 EXHAUST DUCT SHALL TERMINATE 6 FT. ABOVE THE ROOF.
 PER NFPA 33 AND 501.2.1 LOCATION OF EXHAUST OUTLETS.
 2010 FBC (M)
  