| 2015-06-12 08:33:09 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15041010 |
| | ADD: 4015 GEOGIA AVE |
| | CONT: FLORIDA FILTRATION & SPRAY BOOTH |
| | TEL: (561)582-5543 |
| | E-MAIL: [email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRI. JUNE 12/ 2015 |
| | ACTION: DENIED |
| | |
| | 1) DISCREPANCY IN PLANS. THE PERMIT APPLICATION |
| | INDICATES THE WORK DESCRIBED UNDER THIS PREMIT AS THE |
| | INSTALATION OF A PAINT SPRAY BOOTH. NOTE THE PLANS |
| | INDICATE THE INSTALATION OF A MIXING ROOM. PLEASE |
| | CORRECT THE DISCREPANCY. FOR THIS REVIEW, I WILL BE |
| | REVIEWING THE PLANS AS INDICATED UNDER THE PERMIT |
| | DESCIPTION, A SPRAY BOOTH. |
| | |
| | 2) SHEET B-2 SHOWS A ROOF PENETRATION BUT THERE IS NO |
| | DETAIL OF THE ADDITIONAL FRAMING AROUND THE NEW |
| | OPENING, ROOF CURB OR FLASHING DETAILS, PLANS INDICATE |
| | THE ROOF TOP EXHAUST IS GOOD FOR 170 MPH, NO ADDITIONAL |
| | SUPPORT IS REQUIRED. FBC-B 1609.4.2. |
| | |
| | 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |