| 2015-06-29 11:06:36 | 6/29/2015 |
| | PROJECT: MOLLY'S TROLLYS |
| | PERMIT#:15041009 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 3RD ELECTRICAL PLAN REVIEW |
| | ACTION: APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN |
| | APPROVED PROVISIONALLY. FAILURE TO CORRECT THE LISTED |
| | DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED |
| | INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION |
| | FEE(S). |
| | |
| | 1) MANUFACTURER'S PRODUCT APPROVALS INDICATING THE |
| | POWER AND LISTING REQUIREMENTS FOR ALL OF THE |
| | COMPONENETS INVOLVED. |
| | |
| | 2) NEC 514.11 CIRCUIT DISCONNECTS. |
| | (A) GENERAL. EACH CIRCUIT LEADING TO OR THROUGH |
| | DISPENSING EQUIPMENT, INCLUDING EQUIPMENT FOR REMOTE |
| | PUMPING SYSTEMS, SHALL BE PROVIDED WITH A CLEARLY |
| | IDENTIFIED AND READILY ACCESSIBLE SWITCH OR OTHER |
| | ACCEPTABLE MEANS, LOCATED REMOTE FROM THE DISPENSING |
| | DEVICES, TO DISCONNECT SIMULTANEOUSLY FROM THE SOURCE |
| | OF SUPPLY, ALL CONDUCTORS OF THE CIRCUITS, INCLUDING |
| | THE GROUNDED CONDUCTOR, IF ANY. SINGLE-POLE BREAKERS |
| | UTILIZING HANDLE TIES SHALL NOT BE PERMITTED. |
| | |
| | (B) ATTENDED SELF-SERVICE MOTOR FUEL DISPENSING |
| | FACILITIES. EMERGENCY CONTROLS AS SPECIFIED IN |
| | 514.11(A) SHALL BE INSTALLED AT A LOCATION ACCEPTABLE |
| | TO THE AUTHORITY HAVING JURISDICTION, BUT CONTROLS |
| | SHALL NOT BE MORE THAN 30 M (100 FT) FROM DISPENSERS. |
| | [30A:6.7.1] |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |
| | |
| | |
| | |
| | |