2015-06-29 11:06:366/29/2015
 PROJECT: MOLLY'S TROLLYS
 PERMIT#:15041009
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 3RD ELECTRICAL PLAN REVIEW
 ACTION: APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN
 APPROVED PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION
 FEE(S).
  
 1) MANUFACTURER'S PRODUCT APPROVALS INDICATING THE
 POWER AND LISTING REQUIREMENTS FOR ALL OF THE
 COMPONENETS INVOLVED.
  
 2) NEC 514.11 CIRCUIT DISCONNECTS.
 (A) GENERAL. EACH CIRCUIT LEADING TO OR THROUGH
 DISPENSING EQUIPMENT, INCLUDING EQUIPMENT FOR REMOTE
 PUMPING SYSTEMS, SHALL BE PROVIDED WITH A CLEARLY
 IDENTIFIED AND READILY ACCESSIBLE SWITCH OR OTHER
 ACCEPTABLE MEANS, LOCATED REMOTE FROM THE DISPENSING
 DEVICES, TO DISCONNECT SIMULTANEOUSLY FROM THE SOURCE
 OF SUPPLY, ALL CONDUCTORS OF THE CIRCUITS, INCLUDING
 THE GROUNDED CONDUCTOR, IF ANY. SINGLE-POLE BREAKERS
 UTILIZING HANDLE TIES SHALL NOT BE PERMITTED.
  
 (B) ATTENDED SELF-SERVICE MOTOR FUEL DISPENSING
 FACILITIES. EMERGENCY CONTROLS AS SPECIFIED IN
 514.11(A) SHALL BE INSTALLED AT A LOCATION ACCEPTABLE
 TO THE AUTHORITY HAVING JURISDICTION, BUT CONTROLS
 SHALL NOT BE MORE THAN 30 M (100 FT) FROM DISPENSERS.
 [30A:6.7.1]
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,