| 2015-06-04 06:59:16 | 1) SUBMIT TIE-DOWN ENGINEERING FOR THE PROPANE TANK PER |
| | 2010 FBC-FUEL GAS SEC. 301.10.THE RESPONSE FROM |
| | AMERIGAS STATES THERE ARE SIGNED AND SEALED DRAWINGS |
| | FROM AN ENGINEER BUT THERE ARE NO DRAWINGS FOR THE |
| | ANCHORING OF THE TANK FROM AN ENGINEER. CLARIFY. 2ND |
| | REQUEST. |
| | 2) THE PLAN FROM SUPERIOR ENERGY SYSTEMS IS SIGNED AND |
| | SEALED BY AN ENGINEER REGISTERED IN THE THE STAE OF |
| | OHIO. THIS IS UNACCEPTABLE. IF THE DOCUMENTS ARE GOING |
| | TO BE SIGNED AND SEALED BY AN ENGINEER, THE ENGINEER |
| | SHALL BE REGISTERED IN THE STATE OF FLORIDA PER F.S> |
| | 471 & FL. ADMIN. CODE RULE 61G15-23.002. |
| | 3) THE SUBMITTED PLANS DO NOT SHOW COMPLIANCE WITH THE |
| | FOLLOWING REQUIREMENTS OF NFPA 58. PLEASE SHOW |
| | COMPLIANCE WITH THE FOLLOWING CODE SECTION REQUIREMENTS |
| | ON THE PLANS. IDENTIFY ALL COMPONENTS OF THE PIPING |
| | SYSTEM: |
| | A) THE FUEL DISPENSER SHALL BE INSTALLED IN ACCORDANCE |
| | WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS PER |
| | NFPA 58 SEC.6.22.3.1. SUBMIT TWO COPIES OF THE |
| | INSTALLATION INSTRUCTIONS. |
| | B) THE PIPING AND THE DISPENSING HOSE SHALL BE PROVIDED |
| | WITH HYDROSTATIC RELIEF VALVES PER NFPA 58 SEC. |
| | 6.22.3.6 & NFPA SEC. 6.11. |
| | C) AN IDENTIFIED AND ACCESSIBLE SWITCH SHALL BE |
| | INSTALLED AT A LOCATION NOT LESS THAN 20 FT. OR MORE |
| | THAN 100 FT. FROM THE DISPENSING DEVICE TO SHUT OFF THE |
| | POWER PER NFPA 58 SEC. 6.22.3.11. SHOW THE DISTANCE OF |
| | THE EMERGENCY SHUTOFF SWITCH FROM THE DISPENSER. |
| | D) THE HOSE LENGTH FROM THE DISPENSER SHALL NOT EXCEED |
| | 18 FT. NFPA 58 SEC. 6.222.4.1 (1). ALL HOSES SHALL |
| | LISTED FOR USE WITH LP GAS. |
| | E) A LISTED EMERGENCY BREAKAWAY DEVICE COMPLYING WITH |
| | UL 567 SHALL BE INSTALLED ON THE DISPENSER HOSE.NFPA 58 |
| | SEC.6.22.4.2. |
| | |