| 2015-06-09 16:57:01 | 5/2/2015 |
| | PROJECT: MOLLY'S TROLLYS |
| | PERMIT#:15041009 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | PLEASE PROVIDE ELECTRICAL PLANS AND SPECIFICATIONS THAT |
| | CLEARLY INDICATE THE ENTIRE ESCOPE OF THE PROJECT |
| | INCLUDING BUT NOT LIMITED TO THE FOLLOWING: |
| | |
| | 1) MANUFACTURER'S PRODUCT APPROVALS INDICATING THE |
| | POWER AND LISTING REQUIREMENTS FOR ALL OF THE |
| | COMPONENETS INVOLVED. |
| | 2) A SITE PLAN INDICATING THE LOCATION OF THE SOURCE OF |
| | POWER INCLUDING A PANEL SCHEDULE WITH THE ELECTRICAL |
| | CIRCUITS OCPD AND WIRE SIZES PROPOSED. |
| | 3) A SITE PLAN INDICATING THE LOCATIONS FOR THE PUMPS, |
| | DISPENSER(S) CONTROLERS, DISCONNECTS AND EPO'S |
| | (EMERGENCY POWER OFF), |
| | 4) A SITE PLAN INDICATING THE LOCATIONS, PHOTOMETRIC |
| | DETAIL AND CIRCUITING OF THE LUMINAIRS (EXISTING OR |
| | NEW) FOR ILLUMINATION OF THE EQUIPMENT. |
| | 5) A DETAILED PIPING AND CIRCUITING PLAN INDICATING THE |
| | ELECTRICAL CONNECTION OF ALL THE AFOREMENTIONED |
| | COMPONENETS BETWEEN THE SOURCE AND LOADS FOR THE ENTIRE |
| | SCOPE OF WORK PROPOSED. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |
| | |
| | |
| | |
| | |