Plan Review Notes
Plan Review Notes For Permit 15041009
Permit Number 15041009
Review Stop E
Sequence Number 2
Notes
Date Text
2015-06-09 16:57:015/2/2015
 PROJECT: MOLLY'S TROLLYS
 PERMIT#:15041009
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 PLEASE PROVIDE ELECTRICAL PLANS AND SPECIFICATIONS THAT
 CLEARLY INDICATE THE ENTIRE ESCOPE OF THE PROJECT
 INCLUDING BUT NOT LIMITED TO THE FOLLOWING:
  
 1) MANUFACTURER'S PRODUCT APPROVALS INDICATING THE
 POWER AND LISTING REQUIREMENTS FOR ALL OF THE
 COMPONENETS INVOLVED.
 2) A SITE PLAN INDICATING THE LOCATION OF THE SOURCE OF
 POWER INCLUDING A PANEL SCHEDULE WITH THE ELECTRICAL
 CIRCUITS OCPD AND WIRE SIZES PROPOSED.
 3) A SITE PLAN INDICATING THE LOCATIONS FOR THE PUMPS,
 DISPENSER(S) CONTROLERS, DISCONNECTS AND EPO'S
 (EMERGENCY POWER OFF),
 4) A SITE PLAN INDICATING THE LOCATIONS, PHOTOMETRIC
 DETAIL AND CIRCUITING OF THE LUMINAIRS (EXISTING OR
 NEW) FOR ILLUMINATION OF THE EQUIPMENT.
 5) A DETAILED PIPING AND CIRCUITING PLAN INDICATING THE
 ELECTRICAL CONNECTION OF ALL THE AFOREMENTIONED
 COMPONENETS BETWEEN THE SOURCE AND LOADS FOR THE ENTIRE
 SCOPE OF WORK PROPOSED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  
  
  
  