| Plan Review Notes For Permit 15041009 |
| Permit Number |
15041009 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-05-04 11:51:57 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PROVIDE DIMENSIONS FROM EACH PROPERTY LINE. | | | | | | PROVIDE INFORMATION INDICATING THAT THE TANK IS DOUBLED | | | WALLED. | | | | | | PROVIDE PIPING DETAIL FOR DISPENSER AND TANK. | | | | | | PROVIDE LOCATION OF EMERGENCY SHUT OFF. | | | | | | PROVIDE LOCATION OF FIRE EXTINGUISHERS. | | | | | | PROVIDE LOCATION OF NO SMOKING SIGNS. | | | | | | TANK SHALL BE ENCLOSED IN A FENCE IF THE ENTIRE | | | PROPEORTY IS NOT FENCED. PROVIDE NOTE INDICATING FENCE. | | | | | | ALL INSTALLATONS SHALL COMPLY WITH NFPA 1, 101, 30A AND | | | 58. | | | THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE | | | 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING | | | THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER | | | APPLICABLE CODES OR STANDARDS. | | | FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS | | | OF NFPA 10, 2010 EDITION. | | | ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION. | | | NFPA 58, LIQUEFIED PETROLEUM GAS CODE, 2011 EDITION. | | | NFPA 30A, CODE FOR MOTOR FUEL DISPENSING FACILITIES AND | | | REPAIR GARAGES, 2012 EDITION. |
|