Plan Review Notes
Plan Review Notes For Permit 15041009
Permit Number 15041009
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2015-05-04 11:51:57THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PROVIDE DIMENSIONS FROM EACH PROPERTY LINE.
  
 PROVIDE INFORMATION INDICATING THAT THE TANK IS DOUBLED
 WALLED.
  
 PROVIDE PIPING DETAIL FOR DISPENSER AND TANK.
  
 PROVIDE LOCATION OF EMERGENCY SHUT OFF.
  
 PROVIDE LOCATION OF FIRE EXTINGUISHERS.
  
 PROVIDE LOCATION OF NO SMOKING SIGNS.
  
 TANK SHALL BE ENCLOSED IN A FENCE IF THE ENTIRE
 PROPEORTY IS NOT FENCED. PROVIDE NOTE INDICATING FENCE.
  
 ALL INSTALLATONS SHALL COMPLY WITH NFPA 1, 101, 30A AND
 58.
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2010 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION.
 NFPA 58, LIQUEFIED PETROLEUM GAS CODE, 2011 EDITION.
 NFPA 30A, CODE FOR MOTOR FUEL DISPENSING FACILITIES AND
 REPAIR GARAGES, 2012 EDITION.