| Plan Review Notes For Permit 15041000 |
| Permit Number |
15041000 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-06-01 15:06:32 | PLAN DENIED | | | 1) PROVIDE OUTSIDE AIR CALCULATIONS ON PLANS | | | PER TABLE 403.3 FBC (M) 2010 | | | 2) ABANDONED EQUIPMENT MUST BE REMOVED FROM THE | | | ROOF AND SEAL CURB WATER TIGHT | | | 3) PROVIDE A DETAIL FROM THE ENGINEER ON THE | | | EXHAUST FAN CURB TO ROOF AND FAN TO CURB, PROVIDE | | | TYPE AND SIZE OF ANCHOR USED. PER SECTION | | | 301.12 WIND RESISTANCE FBC (M) 2010 | | | 4) REFER TO SECTION 503.2.5.4 SHUT OFF | | | DAMPER CONTROLS FOR FRESH AIR. 2010 | | | FLORIDA ENERGY CODE | | | 5) PROVIDE ENERGY CALCULATIONS PER SECTION | | | 503.2.1 FLORIDA ENERGY CODE 2010 | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|