| Date |
Text |
| 2015-06-03 08:10:21 | 6/3/2015 |
| | PROJECT: REMODEL |
| | PERMIT#: 15040958 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 2ND ELECTRICAL PLAN REVIEW |
| | ACTION: APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN |
| | APPROVED PROVISIONALLY. FAILURE TO CORRECT THE LISTED |
| | DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED |
| | INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION |
| | FEE(S). |
| | |
| | 1) LUMINAIRES IN CLOTHES CLOSETS SHALL BE INSTALLED IN |
| | ACCORDANCE WITH THE PROVISIONS OF THE NEC 410.16(A) AND |
| | (B). |
| | |
| | 2) RECESSED LUMINAIRES INSTALLED IN THE BUILDING |
| | THERMAL ENVELOPE SHALL BE IC AND AIR TIGHT RATED AND |
| | SEALED TO LIMIT AIR LEAKAGE BETWEEN CONDITIONED AND |
| | UNCONDITIONED SPACES. FBC-E 502.3.8 RECESSED LIGHTING. |
| | |
| | 3) IN ADDITION TO THE NUMBER OF BRANCH CIRCUITS |
| | REQUIRED BY OTHER PARTS OF THIS SECTION, AT LEAST ONE |
| | 20-AMPERE BRANCH CIRCUIT SHALL BE PROVIDED TO SUPPLY |
| | BATHROOM RECEPTACLE OUTLET(S). SUCH CIRCUITS SHALL HAVE |
| | NO OTHER OUTLETS. NEC 210.11(C)(3) |
| | |
| | 4) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY |
| | MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS |
| | ARE REQUIRED FOR SITE LIGHTING, SECURITY, CCTV, |
| | AUDIO/VIDEO, NETWORK, DATA, AND, COMMUNICATION WORK. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |