| 2015-05-16 15:33:43 | 5/16/2015 |
| | PROJECT: 330 FRANKLIN RD |
| | PERMIT#: 15040958 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | NO ELECTRICAL PLANS HAVE BEEN SUBMITTED WITH THIS |
| | APPLICATION. NO ELECTRICAL REVIEW HAS BEEN PERFORMED AT |
| | THIS TIME. |
| | |
| | 1) THE ARCHITECTUAL PLANS SUBMITTED WITH THIS |
| | APPLICATION INDICATE THE INSTALLATION OF SEVERAL |
| | ELECTRICAL ELEMENTS ASSOCIATED WITH THE RENOVATION OF A |
| | KITCHEN AND BATHROOM OF AN EXISTING SINGLE FAMILY |
| | DWELLING. PROVIDE COMPLETE ELECTRICAL PLANS DETALAILING |
| | THE INSTALLATION OR RENNOVATION OF THESE ELEMENTS |
| | INCLUDING BUT NOT LIMITED TO THE FOLLOWING: |
| | |
| | 2) A PANEL SCHEDULE INDICATING THE ALL CIRCUIT NUMBERS |
| | AND CORRESPONDING OCPD AND WRE SIZES. NEC 408.4 |
| | |
| | 3) ALL ELEMENTS INVOLVED IN THE RENOVATION INDICATED ON |
| | A FLOOR PLAN WITH CIRCUIT NUMBERS CORRESPONDING TO THE |
| | PANEL SCHEDULE. WPB AMENDMENTS TO FBC 107.3.5.1.2 |
| | |
| | 4) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER |
| | RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11 |
| | |
| | 5) AT LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED IN |
| | BATHROOMS WITHIN (3 FT) OF THE OUTSIDE EDGE OF EACH |
| | BASIN. NEC 210.52 (D) |
| | |
| | 6) RECEPTACLE OUTLETS SHALL BE LOCATED ON BRANCH |
| | CIRCUITS IN ACCORDANCE WITH PART III OF ARTICLE 210. |
| | GENERAL INSTALLATION REQUIREMENTS SHALL BE IN |
| | ACCORDANCE WITH 406.3(A) THROUGH (F). (D) REPLACEMENT |
| | OF RECEPTACLES SHALL COMPLY WITH 406.3(D)(1),(2), AND |
| | (3) AS APPLICABLE. NEC 406.3 |
| | |
| | 7) IN EVERY KITCHEN, FAMILY ROOM, DINING ROOM, LIVING |
| | ROOM, PARLOR, LIBRARY, DEN, SUNROOM, BEDROOM, |
| | RECREATION ROOM, OR SIMILAR ROOM OR AREA OF DWELLING |
| | UNITS, RECEPTACLE OUTLETS SHALL BE INSTALLED IN |
| | ACCORDANCE WITH THE GENERAL PROVISIONS SPECIFIED IN NEC |
| | 210.52(A)(1) THROUGH (A)(3). |
| | |
| | 8) A RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH WALL |
| | COUNTERTOP SPACE THAT IS 300 MM (12 IN.) OR WIDER. |
| | RECEPTACLE OUTLETS SHALL BE INSTALLED SO THAT NO POINT |
| | ALONG THE WALL LINE IS MORE THAN 600 MM (24 IN.) |
| | MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET IN THAT |
| | SPACE.NEC 210.52(C)(1) |
| | |
| | 9) INDICATE AND PROVIDE OR VERIFY ALL REQUIRED SMOKE |
| | AND/OR CARBON MONOXIDE DETECTORS. FBC-R 314-315 |
| | |
| | ONCE ELECTRICAL PLANS HAVE BEEN SUBMITTED AND A REVIEW |
| | CAN BE COMPLETED ADDITIONAL ELERICAL REVIEW |
| | DEFICIENCIES MAY BE FOUND. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |