Plan Review Notes
Plan Review Notes For Permit 15040957
Permit Number 15040957
Review Stop B
Sequence Number 3
Notes
Date Text
2015-07-13 14:28:38BUILDING REVIEW COMMENTS FOR E-MAILED INFORMATION SENT
 BY MRS. MICKEY RUDICK:
  
 1- USP PRODUCT APPROVALS SUBMITTED:
 A) THE USP PRODUCT APPROVAL FL6223-R3 IS FOR THE 2014
 FBC AND IS PENDING APPROVAL. THIS ONE CAN NOT BE USED
 BECAUSE IS NOT APPROVED YET AND IS FOR A DIFFERENT CODE
 VERSION. THE CODE FOR WHICH THIS HOUSE WAS REVIEWED WAS
 FOR 2010 FBC. NEED PRODUCT APPROVAL FOR THE 2010 FBC
 CODE VERSION.
  
 B) THE USP PRODUCT APPROVAL FL859-R4 IS FOR THE 2007
 CODE VERSION. THIS ONE CAN NOT BE USED. THE CODE
 VERSION IS TOO OLD. THE CODE FOR WHICH THIS HOUSE WAS
 REVIEWED WAS FOR 2010 FBC. NEED PRODUCT APPROVAL FOR
 THE 2010 FBC CODE VERSION.
  
 C) THE USP PRODUCT APPROVAL FL6223-R1 IS FOR THE 2007
 CODE VERSION. THIS ONE CAN NOT BE USED. THE CODE
 VERSION IS TOO OLD. THE CODE FOR WHICH THIS HOUSE WAS
 REVIEWED WAS FOR 2010 FBC. NEED PRODUCT APPROVAL FOR
 THE 2010 FBC CODE VERSION.
  
 2- THE PRECAST LINTELS NOA 14-0903.02 SUBMITTED IS OK.
  
 3- SLIDING GLASS DOORS NOA 14-0128.11 SUBMITTED IS OK.
  
  
 BELOW ARE THE COMMENTS THAT MR. ROBERT IS GOING TO TAKE
 CARE OF:
  
 2- ENERGY CALCULATIONS SUBMITTED:
 A) ITEM # 5 STATES THAT CALCULATIONS ARE NOT DONE WORST
 CASE SCENARIO. THEN, WHY THE BUILDING WAS ROTATED 90
 DEGREES AS SPECIFIED ON PAGE 2 OF 6. ALSO WINDOWS AND
 WALLS ON PAGE 3 OF 6 SHOW ROTATED BUILDING ORIENTATION.
 PROVIDE CALCULATIONS THAT SHOW THE ACTUAL ORIENTATION
 OF THE BUILDING. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION. (REPEAT COMMENT. THE ENERGY CALCULATIONS
 NEED TO BE DONE FOR THE ACTUAL ORIENTATION OF THE
 BUILDING. ACCORDING TO THE NORTH ARROW SHOWN ON THE
 SURVEY, THERE ARE NOT NORTH-EAST, EAST-SOUTH,
 SOUTH-WEST, WEST-NORTH, ETC. . REVISE PLANS SHOWING THE
 ACTUAL ORIENTATION NORTH, SOUTH, EAST AND WEST).
  
 B) DOORS ON PAGE 3 OF 6 SPECIFY WOOD DOOR. WHERE IS THE
 WOOD DOOR?. WHY IN BEDROOMS?. SEC. 103.2.2 OF 2010
 FBC-ENERGY CONSERVATION. (REPEAT COMMENT. THE BEDROOM
 SPECIFICATION WAS CHANGED BY HAND TO SAY "GARAGE TO
 HOUSE". HAND CHANGES ARE NOT ALLOWED ON A COMPUTER
 GENERATED PROGRAM. GARAGE NOTES ON SHEET C-1 HAVE THE
 OPTION FOR 3 TYPES OF DOORS, SO SOLID WOOD DOOR MAY NOT
 BE INSTALLED. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION. REVISE AS REQUIRED TO MATCH).
  
 IMPORTANT: LABELS SHOWING THE U-FACTOR AND SHGC FACTOR
 SPECIFIED ON ITEM #7 FOR WINDOWS AND DOORS WILL BE
 VERIFIED IN FIELD.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 *** PLEASE REPLACE AND REMOVED ANY REVISED DRAWING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]