| 2015-07-13 14:28:38 | BUILDING REVIEW COMMENTS FOR E-MAILED INFORMATION SENT |
| | BY MRS. MICKEY RUDICK: |
| | |
| | 1- USP PRODUCT APPROVALS SUBMITTED: |
| | A) THE USP PRODUCT APPROVAL FL6223-R3 IS FOR THE 2014 |
| | FBC AND IS PENDING APPROVAL. THIS ONE CAN NOT BE USED |
| | BECAUSE IS NOT APPROVED YET AND IS FOR A DIFFERENT CODE |
| | VERSION. THE CODE FOR WHICH THIS HOUSE WAS REVIEWED WAS |
| | FOR 2010 FBC. NEED PRODUCT APPROVAL FOR THE 2010 FBC |
| | CODE VERSION. |
| | |
| | B) THE USP PRODUCT APPROVAL FL859-R4 IS FOR THE 2007 |
| | CODE VERSION. THIS ONE CAN NOT BE USED. THE CODE |
| | VERSION IS TOO OLD. THE CODE FOR WHICH THIS HOUSE WAS |
| | REVIEWED WAS FOR 2010 FBC. NEED PRODUCT APPROVAL FOR |
| | THE 2010 FBC CODE VERSION. |
| | |
| | C) THE USP PRODUCT APPROVAL FL6223-R1 IS FOR THE 2007 |
| | CODE VERSION. THIS ONE CAN NOT BE USED. THE CODE |
| | VERSION IS TOO OLD. THE CODE FOR WHICH THIS HOUSE WAS |
| | REVIEWED WAS FOR 2010 FBC. NEED PRODUCT APPROVAL FOR |
| | THE 2010 FBC CODE VERSION. |
| | |
| | 2- THE PRECAST LINTELS NOA 14-0903.02 SUBMITTED IS OK. |
| | |
| | 3- SLIDING GLASS DOORS NOA 14-0128.11 SUBMITTED IS OK. |
| | |
| | |
| | BELOW ARE THE COMMENTS THAT MR. ROBERT IS GOING TO TAKE |
| | CARE OF: |
| | |
| | 2- ENERGY CALCULATIONS SUBMITTED: |
| | A) ITEM # 5 STATES THAT CALCULATIONS ARE NOT DONE WORST |
| | CASE SCENARIO. THEN, WHY THE BUILDING WAS ROTATED 90 |
| | DEGREES AS SPECIFIED ON PAGE 2 OF 6. ALSO WINDOWS AND |
| | WALLS ON PAGE 3 OF 6 SHOW ROTATED BUILDING ORIENTATION. |
| | PROVIDE CALCULATIONS THAT SHOW THE ACTUAL ORIENTATION |
| | OF THE BUILDING. SEC. 103.2.2 OF 2010 FBC-ENERGY |
| | CONSERVATION. (REPEAT COMMENT. THE ENERGY CALCULATIONS |
| | NEED TO BE DONE FOR THE ACTUAL ORIENTATION OF THE |
| | BUILDING. ACCORDING TO THE NORTH ARROW SHOWN ON THE |
| | SURVEY, THERE ARE NOT NORTH-EAST, EAST-SOUTH, |
| | SOUTH-WEST, WEST-NORTH, ETC. . REVISE PLANS SHOWING THE |
| | ACTUAL ORIENTATION NORTH, SOUTH, EAST AND WEST). |
| | |
| | B) DOORS ON PAGE 3 OF 6 SPECIFY WOOD DOOR. WHERE IS THE |
| | WOOD DOOR?. WHY IN BEDROOMS?. SEC. 103.2.2 OF 2010 |
| | FBC-ENERGY CONSERVATION. (REPEAT COMMENT. THE BEDROOM |
| | SPECIFICATION WAS CHANGED BY HAND TO SAY "GARAGE TO |
| | HOUSE". HAND CHANGES ARE NOT ALLOWED ON A COMPUTER |
| | GENERATED PROGRAM. GARAGE NOTES ON SHEET C-1 HAVE THE |
| | OPTION FOR 3 TYPES OF DOORS, SO SOLID WOOD DOOR MAY NOT |
| | BE INSTALLED. SEC. 103.2.2 OF 2010 FBC-ENERGY |
| | CONSERVATION. REVISE AS REQUIRED TO MATCH). |
| | |
| | IMPORTANT: LABELS SHOWING THE U-FACTOR AND SHGC FACTOR |
| | SPECIFIED ON ITEM #7 FOR WINDOWS AND DOORS WILL BE |
| | VERIFIED IN FIELD. |
| | |
| | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | *** PLEASE REPLACE AND REMOVED ANY REVISED DRAWING. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | (561)805-6712 |
| | [email protected] |