Plan Review Notes
Plan Review Notes For Permit 15040957
Permit Number 15040957
Review Stop M
Sequence Number 2
Notes
Date Text
2015-07-10 08:51:352ND REVIEW: FBC 20140 MECHANICAL
 PERMIT #15040957 7/10/15
  
 1) THE NORTH ARROW DIRECTION ON THE REVISED AC PLAN
 DOES NOT MATCH THE NORTH ARROW DIRECTION ON THE NEW
 SURVEY: PLEASE CORRECT.
 2) BASED ON THE NORTH DIRECTIONAL ARROW SHOWN ON THE
 NEW SURVEY (WHICH APPEARS CORRECT BY PAPA MAPPING), THE
 WINDOW DIRECTIONAL ORIENTATIONS ON THE AC SIZING
 CALCULATIONS ARE INCORRECT: PLEASE REVISE THE
 CALCULATIONS.
 3) THE AC PLAN NOTES INDICATES THE CONDENSATE PIPES
 WILL BE RUN THROUGH THE ATTIC, HOWEVER THE NOTES ALSO
 INDICATE THE AHU'S WILL BE HUNG FROM THE GARAGE
 CEILING. WILL A CONDENSATE PUMP BE INSTALLED?
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  