| Plan Review Notes For Permit 15040957 |
| Permit Number |
15040957 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-07-10 08:51:35 | 2ND REVIEW: FBC 20140 MECHANICAL | | | PERMIT #15040957 7/10/15 | | | | | | 1) THE NORTH ARROW DIRECTION ON THE REVISED AC PLAN | | | DOES NOT MATCH THE NORTH ARROW DIRECTION ON THE NEW | | | SURVEY: PLEASE CORRECT. | | | 2) BASED ON THE NORTH DIRECTIONAL ARROW SHOWN ON THE | | | NEW SURVEY (WHICH APPEARS CORRECT BY PAPA MAPPING), THE | | | WINDOW DIRECTIONAL ORIENTATIONS ON THE AC SIZING | | | CALCULATIONS ARE INCORRECT: PLEASE REVISE THE | | | CALCULATIONS. | | | 3) THE AC PLAN NOTES INDICATES THE CONDENSATE PIPES | | | WILL BE RUN THROUGH THE ATTIC, HOWEVER THE NOTES ALSO | | | INDICATE THE AHU'S WILL BE HUNG FROM THE GARAGE | | | CEILING. WILL A CONDENSATE PUMP BE INSTALLED? | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|