Plan Review Notes
Plan Review Notes For Permit 15040957
Permit Number 15040957
Review Stop B
Sequence Number 2
Notes
Date Text
2015-07-10 15:38:43BUILDING REVIEW COMMENTS;
  
 ****NOTE: BUILDING REVIEW MAY BE APPROVED WITH PROVISO.
 THE PERMIT MAY BE ISSUED AND THESE COMMENTS MAY BE
 ADDRESSED AS "REVISIONS" AFTER THE PERMIT IS ISSUED.
 FEES MAY APPLY. PLEASE ADVICE IF YOU WANT THE PROVISO
 OPTION.
  
  
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) USP STRUCTURAL CONNECTORS SPECIFIED ON PLANS AND ALL
 DETAILS. (FLORIDA PRODUCT APPROVALS FL6223-R1 AND FL
 859-R4 SUBMITTED ARE FOR 2007 FBC. NEED PRODUCT
 APPROVALS FOR CURRENT 2010 FBC, WHICH IS THE CODE
 ADOPTED FOR THIS PERMIT APPLICATION).
  
 B) ALL PRECAST LINTELS SPECIFIED ON PLANS. (NOA
 13-0321.07 SUBMITTED IS FOR 4", 6" AND 12" PRECAST
 LINTELS. THESE LINTELS ARE NOT SPECIFIED ON PLANS.
 PROVIDE CORRECT PRODUCT APPROVAL THAT MATCHES LINTELS
 SPECIFIED ON PLANS).
  
 C) NEW COMMENT: SLIDING GLASS DOORS A SHOWN ON PLANS.
 NEW NOA 15-0106.08 SUBMITTED DOESN'T COVER SIZES SHOWN
 ON PLANS. PLANS CALL FOR 10'-0" HIGH DOORS. (NOA
 14-0128.11 SUBMITTED THE FIRS TIME WAS OK.)
  
 2- ENERGY CALCULATIONS SUBMITTED:
 A) ITEM # 5 STATES THAT CALCULATIONS ARE NOT DONE WORST
 CASE SCENARIO. THEN, WHY THE BUILDING WAS ROTATED 90
 DEGREES AS SPECIFIED ON PAGE 2 OF 6. ALSO WINDOWS AND
 WALLS ON PAGE 3 OF 6 SHOW ROTATED BUILDING ORIENTATION.
 PROVIDE CALCULATIONS THAT SHOW THE ACTUAL ORIENTATION
 OF THE BUILDING. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION. (REPEAT COMMENT. THE ENERGY CALCULATIONS
 NEED TO BE DONE FOR THE ACTUAL ORIENTATION OF THE
 BUILDING. ACCORDING TO THE NORTH ARROW SHOWN ON THE
 SURVEY, THERE ARE NOT NORTH-EAST, EAST-SOUTH,
 SOUTH-WEST, WEST-NORTH, ETC. . REVISE PLANS SHOWING THE
 ACTUAL ORIENTATION NORTH, SOUTH, EAST AND WEST).
  
 B) DOORS ON PAGE 3 OF 6 SPECIFY WOOD DOOR. WHERE IS THE
 WOOD DOOR?. WHY IN BEDROOMS?. SEC. 103.2.2 OF 2010
 FBC-ENERGY CONSERVATION. (REPEAT COMMENT. THE BEDROOM
 SPECIFICATION WAS CHANGED BY HAND TO SAY "GARAGE TO
 HOUSE". HAND CHANGES ARE NOT ALLOWED ON A COMPUTER
 GENERATED PROGRAM. GARAGE NOTES ON SHEET C-1 HAVE THE
 OPTION FOR 3 TYPES OF DOORS, SO SOLID WOOD DOOR MAY NOT
 BE INSTALLED. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION. REVISE AS REQUIRED TO MATCH).
  
 IMPORTANT: LABELS SHOWING THE U-FACTOR AND SHGC FACTOR
 SPECIFIED ON ITEM #7 FOR WINDOWS AND DOORS WILL BE
 VERIFIED IN FIELD.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 *** PLEASE REPLACE AND REMOVED ANY REVISED DRAWING.
  