| 2015-07-10 15:38:43 | BUILDING REVIEW COMMENTS; |
| | |
| | ****NOTE: BUILDING REVIEW MAY BE APPROVED WITH PROVISO. |
| | THE PERMIT MAY BE ISSUED AND THESE COMMENTS MAY BE |
| | ADDRESSED AS "REVISIONS" AFTER THE PERMIT IS ISSUED. |
| | FEES MAY APPLY. PLEASE ADVICE IF YOU WANT THE PROVISO |
| | OPTION. |
| | |
| | |
| | 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) USP STRUCTURAL CONNECTORS SPECIFIED ON PLANS AND ALL |
| | DETAILS. (FLORIDA PRODUCT APPROVALS FL6223-R1 AND FL |
| | 859-R4 SUBMITTED ARE FOR 2007 FBC. NEED PRODUCT |
| | APPROVALS FOR CURRENT 2010 FBC, WHICH IS THE CODE |
| | ADOPTED FOR THIS PERMIT APPLICATION). |
| | |
| | B) ALL PRECAST LINTELS SPECIFIED ON PLANS. (NOA |
| | 13-0321.07 SUBMITTED IS FOR 4", 6" AND 12" PRECAST |
| | LINTELS. THESE LINTELS ARE NOT SPECIFIED ON PLANS. |
| | PROVIDE CORRECT PRODUCT APPROVAL THAT MATCHES LINTELS |
| | SPECIFIED ON PLANS). |
| | |
| | C) NEW COMMENT: SLIDING GLASS DOORS A SHOWN ON PLANS. |
| | NEW NOA 15-0106.08 SUBMITTED DOESN'T COVER SIZES SHOWN |
| | ON PLANS. PLANS CALL FOR 10'-0" HIGH DOORS. (NOA |
| | 14-0128.11 SUBMITTED THE FIRS TIME WAS OK.) |
| | |
| | 2- ENERGY CALCULATIONS SUBMITTED: |
| | A) ITEM # 5 STATES THAT CALCULATIONS ARE NOT DONE WORST |
| | CASE SCENARIO. THEN, WHY THE BUILDING WAS ROTATED 90 |
| | DEGREES AS SPECIFIED ON PAGE 2 OF 6. ALSO WINDOWS AND |
| | WALLS ON PAGE 3 OF 6 SHOW ROTATED BUILDING ORIENTATION. |
| | PROVIDE CALCULATIONS THAT SHOW THE ACTUAL ORIENTATION |
| | OF THE BUILDING. SEC. 103.2.2 OF 2010 FBC-ENERGY |
| | CONSERVATION. (REPEAT COMMENT. THE ENERGY CALCULATIONS |
| | NEED TO BE DONE FOR THE ACTUAL ORIENTATION OF THE |
| | BUILDING. ACCORDING TO THE NORTH ARROW SHOWN ON THE |
| | SURVEY, THERE ARE NOT NORTH-EAST, EAST-SOUTH, |
| | SOUTH-WEST, WEST-NORTH, ETC. . REVISE PLANS SHOWING THE |
| | ACTUAL ORIENTATION NORTH, SOUTH, EAST AND WEST). |
| | |
| | B) DOORS ON PAGE 3 OF 6 SPECIFY WOOD DOOR. WHERE IS THE |
| | WOOD DOOR?. WHY IN BEDROOMS?. SEC. 103.2.2 OF 2010 |
| | FBC-ENERGY CONSERVATION. (REPEAT COMMENT. THE BEDROOM |
| | SPECIFICATION WAS CHANGED BY HAND TO SAY "GARAGE TO |
| | HOUSE". HAND CHANGES ARE NOT ALLOWED ON A COMPUTER |
| | GENERATED PROGRAM. GARAGE NOTES ON SHEET C-1 HAVE THE |
| | OPTION FOR 3 TYPES OF DOORS, SO SOLID WOOD DOOR MAY NOT |
| | BE INSTALLED. SEC. 103.2.2 OF 2010 FBC-ENERGY |
| | CONSERVATION. REVISE AS REQUIRED TO MATCH). |
| | |
| | IMPORTANT: LABELS SHOWING THE U-FACTOR AND SHGC FACTOR |
| | SPECIFIED ON ITEM #7 FOR WINDOWS AND DOORS WILL BE |
| | VERIFIED IN FIELD. |
| | |
| | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | *** PLEASE REPLACE AND REMOVED ANY REVISED DRAWING. |
| | |