Plan Review Notes
Plan Review Notes For Permit 15040957
Permit Number 15040957
Review Stop M
Sequence Number 1
Notes
Date Text
2015-06-04 08:46:061ST REVIEW: FBC 2010 RESIDENTIAL & MECHANICAL
  
 1) THE NUMBER OF WINDOWS AND DOORS LISTED IN THE ENERGY
 CALCULATIONS AND THE MANUAL J SIZING CALCS DO NOT MATCH
 THE HOUSE PLANS. SEE SHEET A-1: I AM COUNTING 15
 WINDOWS- EITHER SH OR FIXED GLASS, 2 TRIPLE SGD'S, 2
 SIDE-HINGED DOUBLE DOORS, AND 1 SINGLE SIDE HINGED
 DOORS. THE CALCS ARE LISTING ONLY 14 WINDOWS AND 1 SIDE
 HINGED DOOR.
 PLEASE REVISE THE CALCS AND THE AC PLANS: PLACE A NORTH
 ARROW ON THE AC PLANS AND NUMBER THE WINDOWS AND DOORS
 TO CORRELATE WITH THE CORRECTED CALCULATION SUBMITTALS.
 PLEASE NOTE THE MANUAL J IS INDICATING R38 INSULATION
 ABOVE THE CEILING, HOWEVER THE PLANS ARE INDICATING
 R30.
 2) ENERGY FORM 405-2010: COMPLETE THE CODE COMPLIANCE
 CHECKLIST ON PAGE 6 OF THE CORRECTED SUBMITTAL.
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE WATER
 HEATER AND VENT, AND THE KITCHEN HOOD AND MAKE-UP AIR
 COMPONENTS.
 PLEASE NOTE THE IGNITION SOURCE OF THE WATER HEATER
 SHALL NOT BE LESS THAN 18" ABOVE THE GARAGE FLOOR,
 UNLESS LISTED AS FLAMMABLE VAPOR IGNITION RESISTANT-
 SECTION G2408.2 FBC-10 RES.
 4) THE AC PLAN APPEARS TO INDICATE FLEX DUCTS IN THE
 GARAGE WHICH ARE PROHIBITED PER SECTION R302.5.2
 RESIDENTIAL. UNLESS THE AIR HANDLERS ARE IN THE ATTIC,
 STEEL DUCTS OR DUCT BOARD MUST BE INSTALLED.
 5) SUBMIT TWO COPIES OF THE FL. PRODUCT APPROVAL FOR
 THE BMP CONDENSER TIE-DOWN CLIPS.
  
 CHRISTOPHER COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  