| 2015-06-04 08:46:06 | 1ST REVIEW: FBC 2010 RESIDENTIAL & MECHANICAL |
| | |
| | 1) THE NUMBER OF WINDOWS AND DOORS LISTED IN THE ENERGY |
| | CALCULATIONS AND THE MANUAL J SIZING CALCS DO NOT MATCH |
| | THE HOUSE PLANS. SEE SHEET A-1: I AM COUNTING 15 |
| | WINDOWS- EITHER SH OR FIXED GLASS, 2 TRIPLE SGD'S, 2 |
| | SIDE-HINGED DOUBLE DOORS, AND 1 SINGLE SIDE HINGED |
| | DOORS. THE CALCS ARE LISTING ONLY 14 WINDOWS AND 1 SIDE |
| | HINGED DOOR. |
| | PLEASE REVISE THE CALCS AND THE AC PLANS: PLACE A NORTH |
| | ARROW ON THE AC PLANS AND NUMBER THE WINDOWS AND DOORS |
| | TO CORRELATE WITH THE CORRECTED CALCULATION SUBMITTALS. |
| | PLEASE NOTE THE MANUAL J IS INDICATING R38 INSULATION |
| | ABOVE THE CEILING, HOWEVER THE PLANS ARE INDICATING |
| | R30. |
| | 2) ENERGY FORM 405-2010: COMPLETE THE CODE COMPLIANCE |
| | CHECKLIST ON PAGE 6 OF THE CORRECTED SUBMITTAL. |
| | 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE WATER |
| | HEATER AND VENT, AND THE KITCHEN HOOD AND MAKE-UP AIR |
| | COMPONENTS. |
| | PLEASE NOTE THE IGNITION SOURCE OF THE WATER HEATER |
| | SHALL NOT BE LESS THAN 18" ABOVE THE GARAGE FLOOR, |
| | UNLESS LISTED AS FLAMMABLE VAPOR IGNITION RESISTANT- |
| | SECTION G2408.2 FBC-10 RES. |
| | 4) THE AC PLAN APPEARS TO INDICATE FLEX DUCTS IN THE |
| | GARAGE WHICH ARE PROHIBITED PER SECTION R302.5.2 |
| | RESIDENTIAL. UNLESS THE AIR HANDLERS ARE IN THE ATTIC, |
| | STEEL DUCTS OR DUCT BOARD MUST BE INSTALLED. |
| | 5) SUBMIT TWO COPIES OF THE FL. PRODUCT APPROVAL FOR |
| | THE BMP CONDENSER TIE-DOWN CLIPS. |
| | |
| | CHRISTOPHER COLE |
| | MECHANICAL PLANS EXAMINER |
| | 561-805-6719 |
| | [email protected] |
| | |
| | |