2015-06-01 19:15:23THE FOLLOWING ITEMS SHALL BE CORRECTED AND THE PLANS
 RESUBMITTED FOR A SECOND REVIEW:
  
 THESE PLANS WERE REVIEWED FOR COMPLIANCE WITH THE 2008
 EDITION OF THE NEC, THE 2013 EDITION OF THE NFPA72, THE
 APPLICABLE CHAPTERS OF THE 2010 EDITION OF THE FLORIDA
 BUILDING CODE, FLORIDA BUILDING CODE RESIDENTIAL AND
 FLORIDA BUILDING CODE ENERGY CONSERVATION.
 1. THE SERVICE RISER INDICATES THHN CONDUCTORS TO POOL
 PANEL. PER NEC 300.5(B), IF THESE OR ANY OTHER, WILL
 TRAVEL UNDERGROUND THEY SHALL HAVE AN INSULATION LISTED
 FOR WET LOCATION
 2. ARC-FAULT PROTECTION SHALL BE AS INDICATED IN THE
 CURRENTLY APPLICABLE CODE. 2008 EDITION OF NEC
 3. NOT JUST THOSE BOXES MARKED AS FB, BUT ALL CEILING
 BOXES USED FOR LIGHTING SHALL BE LISTED TO SUPPORT
 50#?S AS INDICATED IN NEC 314.27(A)
 4. EVERY RECEPTACLE O THE EXTERIOR/IN A WET LOCATION
 SHALL BE LISTED AS WEATHER-RESISTANT AS INDICATED IN
 NEC 406.8(B)
 5. NOWHERE ON THE DRAWINGS DID I SEE A NOTE FOR THE
 BONDING OF THE GAS LINE AS INDICATED IN NEC 250.104(B)
  
 AS INDICATED ABOVE, THIS INSTALLATION SHALL COMPLY WITH
 ALL THE ENERGY CONSERVATION REQUIREMENTS OF THE 2010
 FBC-ENERGY CONSERVATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS
  