| 2015-06-01 19:15:23 | THE FOLLOWING ITEMS SHALL BE CORRECTED AND THE PLANS |
| | RESUBMITTED FOR A SECOND REVIEW: |
| | |
| | THESE PLANS WERE REVIEWED FOR COMPLIANCE WITH THE 2008 |
| | EDITION OF THE NEC, THE 2013 EDITION OF THE NFPA72, THE |
| | APPLICABLE CHAPTERS OF THE 2010 EDITION OF THE FLORIDA |
| | BUILDING CODE, FLORIDA BUILDING CODE RESIDENTIAL AND |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION. |
| | 1. THE SERVICE RISER INDICATES THHN CONDUCTORS TO POOL |
| | PANEL. PER NEC 300.5(B), IF THESE OR ANY OTHER, WILL |
| | TRAVEL UNDERGROUND THEY SHALL HAVE AN INSULATION LISTED |
| | FOR WET LOCATION |
| | 2. ARC-FAULT PROTECTION SHALL BE AS INDICATED IN THE |
| | CURRENTLY APPLICABLE CODE. 2008 EDITION OF NEC |
| | 3. NOT JUST THOSE BOXES MARKED AS FB, BUT ALL CEILING |
| | BOXES USED FOR LIGHTING SHALL BE LISTED TO SUPPORT |
| | 50#?S AS INDICATED IN NEC 314.27(A) |
| | 4. EVERY RECEPTACLE O THE EXTERIOR/IN A WET LOCATION |
| | SHALL BE LISTED AS WEATHER-RESISTANT AS INDICATED IN |
| | NEC 406.8(B) |
| | 5. NOWHERE ON THE DRAWINGS DID I SEE A NOTE FOR THE |
| | BONDING OF THE GAS LINE AS INDICATED IN NEC 250.104(B) |
| | |
| | AS INDICATED ABOVE, THIS INSTALLATION SHALL COMPLY WITH |
| | ALL THE ENERGY CONSERVATION REQUIREMENTS OF THE 2010 |
| | FBC-ENERGY CONSERVATION. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS |
| | |