2015-05-26 09:54:39PLAN DENIED
 1) PROVIDE ENERGY CALCULATIONS WITH PLANS
 PER SECTION 603.2 DUCT SIZING 2010 FBC (M)
 AND SECTION 503.2.1 CALCULATION OF HEATING
 AND COOLING LOADS. 2010 FLORIDA ENERGY CODE.
 2) MISSING FIRE DAMPERS REFER TO SECTION
 607.5 FIRE WALLS 2010 FBC (M)
 3) NOTE 2 SHOWS 4" BATH EXHAUST THROUGH
 THE ROOF, NOTE 5 SHOWS 8" BATH EXHAUST THROUGH
 THE ROOF
 4) PROVIDE EQUIPMENT SCHEDULE ON THE PLANS
 SHOWING SEER SECTION 107 2010 FBC
 5) NOTE 10 SHOWS FIRE RATED RETURN AIR
 PLENUM ( MISSING DAMPER )
  