Plan Review Notes
Plan Review Notes For Permit 15040954
Permit Number 15040954
Review Stop M
Sequence Number 1
Notes
Date Text
2015-04-27 09:39:55PLAN DENIED
 1) MISSING FIRE DAMPERS IN SUPPLY DUCT IN
 BEDROOMS. 607.5.1 FIRE WALLS 2010 FBC (M)
 2) FLEX CAN'T PASS THROUGH FIRE RATED WALLS PER
 SECTION 607.7 FLEX DUCT AND CONNECTORS
 2010 FBC (M)
 3) MISSING FIRE DAMPERS SECTION 607.5.1
 FBC (M)
 4) REFER TO TABLE 1509.7 CLEARANCE BELOW
 RAISED ROOF MOUNTED MECHANICAL UNITS.
 2010 FBC.
 5) PROVIDE A NEW DETAIL FROM THE ENGINEER
 SHOWING SIZE AND TYPE OH ANCHOR USED FOR
 CONDENSER STAND TO ROOF AND UNIT TO STAND.
 PER SECTION 301.12 WIND RESISTANCE.
 2010 FBC (M)
 6) SHOW DUCT SIZE FOR THE FRESH AIR ON THE
 PLAN. PER SECTION 107 FBC 2010.
 7) NOTE # 1 SHOWS NEW 2.5 AIR CONDITIONING SYSTEM.
 PROVIDE EQUIPMENT SCHEDULE ON PLANS.PER SECTION
 107 FBC 2010
  