| 2015-04-27 09:39:55 | PLAN DENIED | | | 1) MISSING FIRE DAMPERS IN SUPPLY DUCT IN | | | BEDROOMS. 607.5.1 FIRE WALLS 2010 FBC (M) | | | 2) FLEX CAN'T PASS THROUGH FIRE RATED WALLS PER | | | SECTION 607.7 FLEX DUCT AND CONNECTORS | | | 2010 FBC (M) | | | 3) MISSING FIRE DAMPERS SECTION 607.5.1 | | | FBC (M) | | | 4) REFER TO TABLE 1509.7 CLEARANCE BELOW | | | RAISED ROOF MOUNTED MECHANICAL UNITS. | | | 2010 FBC. | | | 5) PROVIDE A NEW DETAIL FROM THE ENGINEER | | | SHOWING SIZE AND TYPE OH ANCHOR USED FOR | | | CONDENSER STAND TO ROOF AND UNIT TO STAND. | | | PER SECTION 301.12 WIND RESISTANCE. | | | 2010 FBC (M) | | | 6) SHOW DUCT SIZE FOR THE FRESH AIR ON THE | | | PLAN. PER SECTION 107 FBC 2010. | | | 7) NOTE # 1 SHOWS NEW 2.5 AIR CONDITIONING SYSTEM. | | | PROVIDE EQUIPMENT SCHEDULE ON PLANS.PER SECTION | | | 107 FBC 2010 | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|