Plan Review Notes
Plan Review Notes For Permit 15040949
Permit Number 15040949
Review Stop B
Sequence Number 3
Notes
Date Text
2015-07-02 17:38:19PLAN
 REVIEW COMMENTS
  
 3RD REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT A LETTER FROM THE SUCCESSOR ARCHITECT WHICH
 STATES THAT HE IS ADOPTING THE WORK OF THE ORIGINAL
 REGISTERED ARCHITECT AND TAKING PROFESSIONAL AND LEGAL
 RESPONSIBILITY FOR THE CONSTRUCTION DOCUMENTS. THE
 LETTER SHALL STATE THAT THE SUCCESSOR ARCHITECT HAS
 NOTIFIED THE ORIGINAL REGISTERED ARCHITECT BY CERTIFIED
 LETTER OF THE SUCCESSOR'S INTENTIONS TO USE OR REUSE
 THE ORIGINAL REGISTERED ARCHITECT'S WORK AS REQUIRED BY
 F.A.C. 61G1-18.002
  
 2) PROVIDE BUCK FASTENING DETAILS FOR THE EXTERIOR
 DOOR, WINDOW AND SECTIONAL GARAGE DOOR. FBC-R612.10.2.1
  
 3) THE PRODUCT APPROVALS FOR THE PGT PW-701 FIXED
 WINDOWS NOA NO. 13-0502.03 HAVE NOT BEEN APPROVED IN
 WRITING BY THE SUCCESSOR ARCHITECT.
  
 4) THE ROOFING PRODUCT APPROVAL FOR THE FIBERTITE
 SINGLE PLY ROOF SYSTEM (NOA NO. 12-1019.29) IN THE
 SUBMITTAL DOCUMENTS IS FOR USE ON STEEL DECKS. THIS
 GARAGE HAS A 5/8" PLYWOOD DECK. SUBMIT TWO COPIES OF
 ROOFING PRODUCT APPROVALS FOR A WOOD DECK. DCA RULE
 9N-3 AND FBC 107.2.1
  
 5) SPECIFY WHICH ONE OF THE APPROVED ASSEMBLIES LISTED
 IN THE ROOFING PRODUCT APPROVAL WILL BE USED. SPECIFY
 THE ATTACHMENT METHOD AND THE MAXIMUM DESIGN PRESSURE
 FOR THE PROPOSED SYSTEM. IF ENHANCED FASTENING IS
 REQUIRED TO MEET THE HIGHER UPLIFTS IN ROOF ZONES 2 AND
 3, SUBMIT SIGNED AND SEALED RAS 117 CALCULATIONS.
  
  