| 2015-07-02 17:38:19 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 3RD REVIEW: FBC 2010 |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) SUBMIT A LETTER FROM THE SUCCESSOR ARCHITECT WHICH |
| | STATES THAT HE IS ADOPTING THE WORK OF THE ORIGINAL |
| | REGISTERED ARCHITECT AND TAKING PROFESSIONAL AND LEGAL |
| | RESPONSIBILITY FOR THE CONSTRUCTION DOCUMENTS. THE |
| | LETTER SHALL STATE THAT THE SUCCESSOR ARCHITECT HAS |
| | NOTIFIED THE ORIGINAL REGISTERED ARCHITECT BY CERTIFIED |
| | LETTER OF THE SUCCESSOR'S INTENTIONS TO USE OR REUSE |
| | THE ORIGINAL REGISTERED ARCHITECT'S WORK AS REQUIRED BY |
| | F.A.C. 61G1-18.002 |
| | |
| | 2) PROVIDE BUCK FASTENING DETAILS FOR THE EXTERIOR |
| | DOOR, WINDOW AND SECTIONAL GARAGE DOOR. FBC-R612.10.2.1 |
| | |
| | 3) THE PRODUCT APPROVALS FOR THE PGT PW-701 FIXED |
| | WINDOWS NOA NO. 13-0502.03 HAVE NOT BEEN APPROVED IN |
| | WRITING BY THE SUCCESSOR ARCHITECT. |
| | |
| | 4) THE ROOFING PRODUCT APPROVAL FOR THE FIBERTITE |
| | SINGLE PLY ROOF SYSTEM (NOA NO. 12-1019.29) IN THE |
| | SUBMITTAL DOCUMENTS IS FOR USE ON STEEL DECKS. THIS |
| | GARAGE HAS A 5/8" PLYWOOD DECK. SUBMIT TWO COPIES OF |
| | ROOFING PRODUCT APPROVALS FOR A WOOD DECK. DCA RULE |
| | 9N-3 AND FBC 107.2.1 |
| | |
| | 5) SPECIFY WHICH ONE OF THE APPROVED ASSEMBLIES LISTED |
| | IN THE ROOFING PRODUCT APPROVAL WILL BE USED. SPECIFY |
| | THE ATTACHMENT METHOD AND THE MAXIMUM DESIGN PRESSURE |
| | FOR THE PROPOSED SYSTEM. IF ENHANCED FASTENING IS |
| | REQUIRED TO MEET THE HIGHER UPLIFTS IN ROOF ZONES 2 AND |
| | 3, SUBMIT SIGNED AND SEALED RAS 117 CALCULATIONS. |
| | |
| | |