| Plan Review Notes For Permit 15040949 |
| Permit Number |
15040949 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-06-01 18:23:40 | THE FOLLOWING ITEMS SHALL BE CORRECTED AND THE PLANS | | | RESUBMITTED FOR A SECOND REVIEW: | | | | | | | | | THESE PLANS WERE REVIEWED FOR COMPLIANCE WITH THE 2008 | | | EDITION OF THE NEC, THE 2013 EDITION OF THE NFPA72, THE | | | APPLICABLE CHAPTERS OF THE 2010 EDITION OF THE FLORIDA | | | BUILDING CODE, FLORIDA BUILDING CODE RESIDENTIAL AND | | | FLORIDA BUILDING CODE ENERGY CONSERVATION. | | | 1. YOU SHALL SUBMIT A SITE SPECIFIC SERVICE RISER | | | DIAGRAM. | | | 2. YOU NEED TO SPECIFY THE SCOPE OF ALL SITE INSTALLED | | | APPARATUS, AND INCLUDE THAT IN WITH THE ABOVE RISER. | | | 3. NEC 210.70 REQUIRES A LIGHT W/A SWITCH AT THE REAR | | | DOOR OF THE GARAGE. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE | | | PREVIOUSLY REVIEWED SHEETS | | | | | | FOR QUESTIONS ON THE ABOVE, PLEASE CONTACT: | | | MIKE ALBARRAN | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | PH: (561) 805-6743 | | | EMAIL: [email protected] | | | |
|