| Plan Review Notes For Permit 15040900 |
| Permit Number |
15040900 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-05-04 14:00:23 | APPROVED WITH EXCEPTION: IN FUTURE COMPLY WITH THE | | | FOLLOWING MINIMUM PLAN REVIEW CRITERIA. | | | | | | 1) PROVIDE FULL SIZE PLANS THAT ARE LEGIBLE. WPB | | | AMENDMENTS TO FBC 107.2.1.4 | | | BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH | | | SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE | | | MEDIUM. | | | | | | 2) PROVIDE MANUFACTURER EQUIPMENT SUBMITTALS FOR ANY | | | AND ALL EQUIPMENT AND CABLE PROPSED TO BE INSTALLED IN | | | COMPLIANCE WITH NEC 110.3(B). WPB AMENDMENTS TO FBC | | | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | 3) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF | | | THE PERSON RESPONSIBLE FOR THE DESIGN. FBC, WPB | | | AMENDMENTS 107.2.1 | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] |
|