2015-05-14 16:16:23REVIEW BY CHRIS COLE.
  
 1) PROVIDE AC LOAD CALCULATIONS FOR THE NEW SYSTEMS IN
 ACCORDANCE WITH SECTION 503.2.1 FBC-10 ENERGY
 CONSERVATION.
 2) SHEET M111: PROVIDE STRUCTURAL DETAILS FOR ANCHORING
 THE CU ANGLE BRACKETS TO THE EXTERIOR WALLS, AND THE
 CU'S TO THE ANGLE BRACKETS- SECTION 301.12 FMC-10.
 3) M111: THE CONDENSATE FROM THE FCU'S IS NOT PERMITTED
 TO DRAIN INTO THE CITY SANITARY SYSTEM IN COMPLIANCE
 WITH SECTION 90-203, WPB AMENDMENTS TO THE FBC-10
 BUILDING CODE.
 PROVIDE AN ALTERNATE LOCATION.
  
 CHRISTOPHER COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719