| Plan Review Notes For Permit 15040842 |
| Permit Number |
15040842 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-05-14 16:16:23 | REVIEW BY CHRIS COLE. | | | | | | 1) PROVIDE AC LOAD CALCULATIONS FOR THE NEW SYSTEMS IN | | | ACCORDANCE WITH SECTION 503.2.1 FBC-10 ENERGY | | | CONSERVATION. | | | 2) SHEET M111: PROVIDE STRUCTURAL DETAILS FOR ANCHORING | | | THE CU ANGLE BRACKETS TO THE EXTERIOR WALLS, AND THE | | | CU'S TO THE ANGLE BRACKETS- SECTION 301.12 FMC-10. | | | 3) M111: THE CONDENSATE FROM THE FCU'S IS NOT PERMITTED | | | TO DRAIN INTO THE CITY SANITARY SYSTEM IN COMPLIANCE | | | WITH SECTION 90-203, WPB AMENDMENTS TO THE FBC-10 | | | BUILDING CODE. | | | PROVIDE AN ALTERNATE LOCATION. | | | | | | CHRISTOPHER COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|