| Plan Review Notes For Permit 15040841 |
| Permit Number |
15040841 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-05-14 12:04:52 | DISPOSITION AND RESPECTIVE COMMENTS FOR ELECTRICAL PLAN | | | REVIEW | | | | | | APPLICABLE CODES: FBC 2010; WPB AMENDMENTS TO FBC 2010 | | | CHAPTER 1; NEC 2008 | | | REVIEW CYCLE: 1ST ELECTRICAL REVIEW | | | ACTION: FAILED AS INDICATED BELOW: | | | | | | AS PER FBC 107.2.1 SUBMITTAL DOCUMENT SHOULD BE | | | PROPERLY DIMENSIONED AND THOUGH 1/8 SCALE IS | | | ACCEPTABLE, IN THIS CASE THE SHEETS APPEAR TO BE VERY | | | CLUTTERED TO PROPERLY REVIEW THEM. IN LOOKING THROUGH | | | THE SUBMITTAL I NOTICED THAT THE ELECTRICAL RISER | | | DIAGRAM IS MISSING ALONG WITH A LIGHTING DIAGRAM. AS | | | PART OF THE LIGHTING DIAGRAM I WILL NEED TO HAVE A | | | LEGIBLE FIXTURE (LUMINAIRE) SCHEDULE TO BE ABLE TO | | | CHECK FOR EMERGENCY AND EXIT LIGHTING COMPLIANCE. I DID | | | NOTICE THAT THERE IS NO EXIT LIGHTS ON THE ROOF | | | THERE IS A REFERENCE TO ELECTRICAL PAGE E4.1 WHICH IS | | | MISSING. I WAS ALSO ABLE TO NOTICE THAT THE HVAC | | | EQUIPMENT IS MISSING THE SERVICE OUTLET REQUIRED BY NEC | | | 210.63 | | | | | | | | | |
|