| Plan Review Notes For Permit 15040825 |
| Permit Number |
15040825 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-04-22 18:52:59 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. SEE PAGE 6 OF THE PRODUCT APPROVAL. CONTRACTOR HAS | | | PROVIDED THE FASTENING FOR "OPEN" ENCLOSURE. FOR AN | | | ENCLOSED STRUCTURE, FASTENING SHOULD BE ACCORDING TO | | | THE CHART FOR "ENCLOSED" (PAGE NOT INCLUDED). THIS PAGE | | | IS FOR SYSTEM TYPE C: MECHANICALLY ATTACHED INSULATION, | | | BONDED ROOF COVER. | | | | | | PAGE 9 WAS ALSO PROVIDED, SYSTEM TYPE D: INSULATION, | | | MECHANICALLY ATTACHED BASE, BONDED ROOF COVER. | | | | | | IT IS NOT CLEAR WHICH OF THE TWO SYSTEMS IS PROPOSED. | | | PLEASE SELECT ONE. IF SYSTEM C IS SELECTED, PROVIDE THE | | | MISSING PAGE (7) AND REVISE PROPOSED FASTENING TO | | | CORRELATE WITH THE PRODUCT APPROVAL (OR CIRCLE ON | | | PRODUCT APPROVAL). | | | |
|