| Plan Review Notes For Permit 15040823 |
| Permit Number |
15040823 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-04-30 10:54:03 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THE PROPOSED PROJECT INVOLVES REMOVING TWO | | | SEPARATELY CONTROLLED ELEVATOR LOBBIES AND CREATING ONE | | | LOBBY INVOLVING A TWO FLOOR COMMUNICATING SPACE. | | | ADDITIONAL INFORMATION IS REQUIRED REGARDING THE SMOKE | | | PROTECTION OF EITHER THE LOBBY OR THE ELEVATORS. | | | | | | IS THE NEWLY CREATED LOBBY SMOKE CONTROLLED? | | | | | | IS THE ELEVATOR SHAFT(S) SMOKE CONTROLLED? | | | | | | 2) INCORRECT REFERENCES ARE NOTED ON THE FACE PAGE. | | | | | | THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE | | | 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING | | | THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER | | | APPLICABLE CODES OR STANDARDS. | | | FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS | | | OF NFPA 13, 2010 EDITION. | | | FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF | | | NFPA 72, 2010 EDITION. | | | CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF | | | NFPA 241, 2009 EDITION. | | | FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS | | | OF NFPA 10, 2010 EDITION. | | | ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION. | | | | | | |
|