| Plan Review Notes For Permit 15040823 |
| Permit Number |
15040823 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-05-14 16:06:56 | DISPOSITION AND RESPECTIVE COMMENTS FOR ELECTRICAL PLAN | | | REVIEW | | | APPLICABLE CODES: FBC 2010; WPB AMENDMENTS TO FBC 2010 | | | CHAPTER 1; NEC 2008 | | | REVIEW CYCLE: 1ST REVIEW | | | ACTION: FAILED AS INDICATED BELOW | | | | | | 1. I NEED MORE DETAIL ON THE EQUIPMENT ROOM INDICATED | | | ON THE DRAWING AS WELL AS THE FIRE AND MECHANICAL. | | | 2. THE LIGHTING AS SHOWN ON THE PLANS DOES NOT CONFORM | | | WITH THE EMERGENCY LIGHTING REQUIREMENTS. | | | 3. CORRECT THE RISER DIAGRAM |
|