| Plan Review Notes For Permit 15040816 |
| Permit Number |
15040816 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-04-23 13:17:48 | APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN APPROVED | | | PROVISIONALLY. FAILURE TO CORRECT THE LISTED | | | DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED | | | INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION | | | FEE(S). | | | | | | SWIMMING POOL WIRING SHALL COMPLY WITH THE 2008 NEC | | | ARTICLE 680. AND THE 2010 FBC ENERGY BOOK CHAPTER | | | 4.SPECIFICALLY THE FOLLOWING: | | | | | | 1) 680.8 OVERHEAD SERVICE LINES. | | | 2) 680.10 UNDERGROUND WIRING. | | | 3) 680.12 MAINTENANCE DISCONNECTING MEANS. | | | 4) 680.21 MOTORS | | | 5) 680.22(A) AREA LIGHTING AND RECEPTACLES | | | 6) 680.22(B) GFCI PROTECTION. | | | 7) 680.25 FEEDERS. | | | 8) 680.26 EQUIPOTENTIAL BONDING. | | | 9) FBC ENERGY CHAPTER 4. SECTION 403.9 | | | |
|