Plan Review Notes
Plan Review Notes For Permit 15040815
Permit Number 15040815
Review Stop B
Sequence Number 1
Notes
Date Text
2015-05-05 14:39:15****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 FBC 2010 RESIDENTIAL 301, RESISTANCE TO WIND LOADS:
  
 1. TWO COMPLETE SETS OF PLANS REQUIRED FOR PERMIT
 ISSUANCE, FBC 107. FAILURE TO PROVIDE TWO COMPLETE SETS
 MAY RESULT IN ADDITIONAL FEES CHARGED.
  
 2. PROPOSED INSTALLATION NOT CLEAR. VERTICAL
 INSTALLATION, SPAN SHOULD CORRELATE WITH THE OPENING
 SIZE HEIGHT AND EDGE DISTANCE. THIS NUMBER SHOULD BE
 ANCHOR TO ANCHOR.
  
 3. CONCRETE SUBSTRATE IS STATED. THE BOTTOM IS
 TYPICALLY A FILLED CELL OR HOLLOW, NOT FORMED AND
 POURED CONCRETE. PLEASE REVISE OR CLARIFY.
  
 4. 1" EDGE DISTANCE PROPOSED; 3 1/2" REQUIRED OR A
 FACTOR TO BE APPLIED, SEE CHART ON SHEET 5. MINIMUM
 EDGE DISTANCE IS 2" FOR PANELMATE (AND REQUIRED A .5
 FACTOR).
  
 5. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB, FBC
 109.
  
  
  