| Plan Review Notes For Permit 15040815 |
| Permit Number |
15040815 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-05-05 14:39:15 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | FBC 2010 RESIDENTIAL 301, RESISTANCE TO WIND LOADS: | | | | | | 1. TWO COMPLETE SETS OF PLANS REQUIRED FOR PERMIT | | | ISSUANCE, FBC 107. FAILURE TO PROVIDE TWO COMPLETE SETS | | | MAY RESULT IN ADDITIONAL FEES CHARGED. | | | | | | 2. PROPOSED INSTALLATION NOT CLEAR. VERTICAL | | | INSTALLATION, SPAN SHOULD CORRELATE WITH THE OPENING | | | SIZE HEIGHT AND EDGE DISTANCE. THIS NUMBER SHOULD BE | | | ANCHOR TO ANCHOR. | | | | | | 3. CONCRETE SUBSTRATE IS STATED. THE BOTTOM IS | | | TYPICALLY A FILLED CELL OR HOLLOW, NOT FORMED AND | | | POURED CONCRETE. PLEASE REVISE OR CLARIFY. | | | | | | 4. 1" EDGE DISTANCE PROPOSED; 3 1/2" REQUIRED OR A | | | FACTOR TO BE APPLIED, SEE CHART ON SHEET 5. MINIMUM | | | EDGE DISTANCE IS 2" FOR PANELMATE (AND REQUIRED A .5 | | | FACTOR). | | | | | | 5. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB, FBC | | | 109. | | | | | | | | | |
|