Plan Review Notes
Plan Review Notes For Permit 15040809
Permit Number 15040809
Review Stop E
Sequence Number 1
Notes
Date Text
2015-05-04 10:33:11THE PLANS HAVE BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES PRIOR TO INSPECTION
 WILL RESULT IN FAILED INSPECTION(S) AND THE ASSESSMENT
 OF RE-INSPECTION FEE(S).
  
 1) PROVIDE A MAIN SERVICE DISCONNECT AT A READILY
 ACCESSIBLE LOCATION NEAREST THE POINT OF ENTRANCE OF
 THE SERVICE CONDUCTORS. NEC 230.70
  
 2) AN INTERSYSTEM BONDING TERMINATION FOR CONNECTING
 INTERSYSTEM BONDING AND GROUNDING CONDUCTORS REQUIRED
 FOR OTHER SYSTEMS SHALL BE PROVIDED EXTERNAL TO
 ENCLOSURES AT THE SERVICE EQUIPMENT AND AT THE
 DISCONNECTING MEANS FOR ANY ADDITIONAL BUILDINGS OR
 STRUCTURES. NEC 250.94.
  
 3) THE NON?CURRENT-CARRYING METAL PARTS OF EQUIPMENT
 INDICATED IN 250.92(A)(1) AND (A)(2) SHALL BE BONDED
 TOGETHER. NEC 250.92
  
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved