| Plan Review Notes For Permit 15040809 |
| Permit Number |
15040809 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-05-04 10:33:11 | THE PLANS HAVE BEEN APPROVED PROVISIONALLY. FAILURE TO | | | CORRECT THE LISTED DEFICIENCIES PRIOR TO INSPECTION | | | WILL RESULT IN FAILED INSPECTION(S) AND THE ASSESSMENT | | | OF RE-INSPECTION FEE(S). | | | | | | 1) PROVIDE A MAIN SERVICE DISCONNECT AT A READILY | | | ACCESSIBLE LOCATION NEAREST THE POINT OF ENTRANCE OF | | | THE SERVICE CONDUCTORS. NEC 230.70 | | | | | | 2) AN INTERSYSTEM BONDING TERMINATION FOR CONNECTING | | | INTERSYSTEM BONDING AND GROUNDING CONDUCTORS REQUIRED | | | FOR OTHER SYSTEMS SHALL BE PROVIDED EXTERNAL TO | | | ENCLOSURES AT THE SERVICE EQUIPMENT AND AT THE | | | DISCONNECTING MEANS FOR ANY ADDITIONAL BUILDINGS OR | | | STRUCTURES. NEC 250.94. | | | | | | 3) THE NON?CURRENT-CARRYING METAL PARTS OF EQUIPMENT | | | INDICATED IN 250.92(A)(1) AND (A)(2) SHALL BE BONDED | | | TOGETHER. NEC 250.92 | | | | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] |
|