Plan Review Notes
Plan Review Notes For Permit 15040794
Permit Number 15040794
Review Stop P
Sequence Number 5
Notes
Date Text
2015-07-09 08:46:441) THE FOUNTAIN PLANS SHOW THE EQUIPMENT ROOM AS BEING
 ON GRADE. THE EQUIPMENT ROOM IS ACTUALLY BELOW GROUND.
 THERE IS NO LOUVERED DOOR ON THIS ROOM AND THERE IS NO
 WAY TO INSTALL A VENT ON THE OPPOSITE WAL AS NOTED ON
 THE PLANSL. SUBMIT REVISE PLANS SHOWING THE EQUIPMENT
 ROOM BELOW GRADE & LOCATION OF THE EQUIPMENT WITHIN THE
 ROOM. THE LOCATION OF THE EQUIPMENT BELOW GRADE WILL
 ALSO AFFECT THE TOTAL DYNAMIC HEAD.RECHECK THE FLOW
 CALCULATIONS TO CONFIRM COMPLIANCE AND CONFIRM
 COMPLIANCE ON THE PLANS.THE SWIMMING POOL AND THE SPA
 WILL REQUIRE REVISIONS FOR THIS SAME REASON.
 2) SHT. 2 SHOWS THE RETURN LINE AS 2" ON THE ISOMETRIC
 BUT THE FOUNTAIN CROSS SECTION SHOWS IT AS 2 1/2" .
 CLARIFY.
 3) VENTILATION SHALL BE PROVIDED IN ACCORDANCE WITH
 2010 FBC SEC.424.1.5.4. SUBMIT CALCULATIONS.
 4) THE OPENING TO THE EQUIPMENT ROOM SHALL COMPLY WITH
 2010 FBC SEC.424.1.5.5.
  
  
 I SUGGEST SOMEONE CALL ME TO DISCUSS THESE COMMENTS SO
 I CAN PROVIDE THE PROPER DIRECTION.
  
  