| Plan Review Notes For Permit 15040794 |
| Permit Number |
15040794 |
|
| Review Stop |
P |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2015-07-09 08:46:44 | 1) THE FOUNTAIN PLANS SHOW THE EQUIPMENT ROOM AS BEING | | | ON GRADE. THE EQUIPMENT ROOM IS ACTUALLY BELOW GROUND. | | | THERE IS NO LOUVERED DOOR ON THIS ROOM AND THERE IS NO | | | WAY TO INSTALL A VENT ON THE OPPOSITE WAL AS NOTED ON | | | THE PLANSL. SUBMIT REVISE PLANS SHOWING THE EQUIPMENT | | | ROOM BELOW GRADE & LOCATION OF THE EQUIPMENT WITHIN THE | | | ROOM. THE LOCATION OF THE EQUIPMENT BELOW GRADE WILL | | | ALSO AFFECT THE TOTAL DYNAMIC HEAD.RECHECK THE FLOW | | | CALCULATIONS TO CONFIRM COMPLIANCE AND CONFIRM | | | COMPLIANCE ON THE PLANS.THE SWIMMING POOL AND THE SPA | | | WILL REQUIRE REVISIONS FOR THIS SAME REASON. | | | 2) SHT. 2 SHOWS THE RETURN LINE AS 2" ON THE ISOMETRIC | | | BUT THE FOUNTAIN CROSS SECTION SHOWS IT AS 2 1/2" . | | | CLARIFY. | | | 3) VENTILATION SHALL BE PROVIDED IN ACCORDANCE WITH | | | 2010 FBC SEC.424.1.5.4. SUBMIT CALCULATIONS. | | | 4) THE OPENING TO THE EQUIPMENT ROOM SHALL COMPLY WITH | | | 2010 FBC SEC.424.1.5.5. | | | | | | | | | I SUGGEST SOMEONE CALL ME TO DISCUSS THESE COMMENTS SO | | | I CAN PROVIDE THE PROPER DIRECTION. | | | | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | | | | |
|