| 2015-06-25 16:47:54 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS |
| | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE |
| | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO |
| | THE CORRECTIONS NOTED. |
| | |
| | THE FOLLOWING ITEMS SHALL BE CORRECTED AND THE PLANS |
| | RESUBMITTED FOR A SECOND REVIEW: |
| | |
| | 1. AN ELECTRICAL PERMIT SHALL BE REQUIRED FOR THIS |
| | FOUNTAIN. |
| | 2. AS INDICATED IN NEC 680.50, THIS FOUNTAIN SHARES |
| | WATER W/THE POOL. THEREFORE ALL REQUIREMENTS FOR A |
| | PERMANENT POOL SHALL APPLY THUS REQUIRING AN |
| | EQUIPOTENTIAL BOND AROUND THE FOUNTAIN MEETING THE |
| | REQUIREMENTS OF 680.26. |
| | 3. THE ELECTRICAL DIAGRAM OF PAGE 2 OF 2 SHALL BE |
| | AMENDED TO INDICATE THE EXACT PANEL WHERE FOUNTAIN |
| | CONTROL PANEL IS BEING SERVED FROM, FURTHERMORE AS |
| | INDICATED IN NEC 230.70 A PLAQUE INDICATING THE |
| | LOCATION OF SUCH DISCONNECT SHALL BE PLACED ON THAT |
| | SOURCE. |
| | 4. INDICATE ON FLOOR OR SITE PLAN THE LOCATION OF THE |
| | GENERAL PURPOSE RECEPTACLE SHOWN ON THE RISER. IT SHALL |
| | COMPLY W/NEC 210.8, 406.8 & 680.58 |
| | 5. PROVIDE PANEL SCHEDULE AND LOAD CALCS FOR THE |
| | CONTROL PANEL |
| | 6. THIS IS AN OUTDOOR FOUNTAIN, PROVIDE CUT SHEETS ON |
| | LUMINARIES. CONFIRM COMPLIANCE W/NEC 680.23, 680.51 & |
| | W/FBC-E ?505. |
| | |
| | ALL THIS CAN BE ACCOMPLISHED WITH IDENTIFYING NOTES ON |
| | THE DRAWINGS. YOU DON?T HAVE TO DRAW THE ENTIRE RISER |
| | DIAGRAM ALL YOU DO HAVE TO INCLUDE A RISER DIAGRAM |
| | SHOWING THE POWER SOURCE FOR THE CONTROL PANEL. |
| | INDICATE ITS LOCATION AND ADD THE NOTES INDICATED |
| | ABOVE. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO |
| | CONTACT ME. |
| | |
| | RESPECTFULLY SUBMITTED, |
| | |
| | MIKE ALBARRAN |
| | |
| | |