2015-06-25 16:47:54PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE CORRECTIONS NOTED.
  
 THE FOLLOWING ITEMS SHALL BE CORRECTED AND THE PLANS
 RESUBMITTED FOR A SECOND REVIEW:
  
 1. AN ELECTRICAL PERMIT SHALL BE REQUIRED FOR THIS
 FOUNTAIN.
 2. AS INDICATED IN NEC 680.50, THIS FOUNTAIN SHARES
 WATER W/THE POOL. THEREFORE ALL REQUIREMENTS FOR A
 PERMANENT POOL SHALL APPLY THUS REQUIRING AN
 EQUIPOTENTIAL BOND AROUND THE FOUNTAIN MEETING THE
 REQUIREMENTS OF 680.26.
 3. THE ELECTRICAL DIAGRAM OF PAGE 2 OF 2 SHALL BE
 AMENDED TO INDICATE THE EXACT PANEL WHERE FOUNTAIN
 CONTROL PANEL IS BEING SERVED FROM, FURTHERMORE AS
 INDICATED IN NEC 230.70 A PLAQUE INDICATING THE
 LOCATION OF SUCH DISCONNECT SHALL BE PLACED ON THAT
 SOURCE.
 4. INDICATE ON FLOOR OR SITE PLAN THE LOCATION OF THE
 GENERAL PURPOSE RECEPTACLE SHOWN ON THE RISER. IT SHALL
 COMPLY W/NEC 210.8, 406.8 & 680.58
 5. PROVIDE PANEL SCHEDULE AND LOAD CALCS FOR THE
 CONTROL PANEL
 6. THIS IS AN OUTDOOR FOUNTAIN, PROVIDE CUT SHEETS ON
 LUMINARIES. CONFIRM COMPLIANCE W/NEC 680.23, 680.51 &
 W/FBC-E ?505.
  
 ALL THIS CAN BE ACCOMPLISHED WITH IDENTIFYING NOTES ON
 THE DRAWINGS. YOU DON?T HAVE TO DRAW THE ENTIRE RISER
 DIAGRAM ALL YOU DO HAVE TO INCLUDE A RISER DIAGRAM
 SHOWING THE POWER SOURCE FOR THE CONTROL PANEL.
 INDICATE ITS LOCATION AND ADD THE NOTES INDICATED
 ABOVE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 RESPECTFULLY SUBMITTED,
  
 MIKE ALBARRAN
  
  