Plan Review Notes
Plan Review Notes For Permit 15040794
Permit Number 15040794
Review Stop P
Sequence Number 2
Notes
Date Text
2015-06-19 08:26:041) SUBMIT MANUFACTURER SPECS. ON THE MAIN DRAINS BEING
 USED. WPB AMEND. TO 2010 FBC SEC. 107.2.1.2ND REQUEST.
 2) SHOW THE DISTANCE BETWEEN THE TWO MAIN DRAINS.WPB
 AMEND. TO 2010 FBC SEC. 107.2.1.2ND REQUEST.
 3) SUBMIT PUMP CURVE INFO.2ND REQUEST.
 4) SUBMIT SPECS. FOR THE PUMP, SKIMMER AND TABLET
 FEEDER.2ND REQUEST.
 5) THE POTABLE WATER SUPPLY SHALL BE PROTECTED WITH A
 RPZ BACKFLOW PREVENTION DEVICE PER THE CITY OF WPB
 CROSS CONNECTION MANUAL. 2ND REQUEST.
 6) THE PLANS AND ISOMETRIC SHOW A 4" MAIN DRAIN BUT THE
 FOUNTAIN CROSS SECTION SHOWS A 6" MAIN DRAIN. CLARIFY.
 2ND REQUEST.
 7) THE PLAN SHOWS 2" OVERFLOW TO ON-SITE STORM DRAIN.
 CLARIFY "ON-SITE STORM DRAIN. THE OVERDLOW SHALL NOT
 DISCHARGE TO THE STORMWATER SYSTEM PER CITY ORDINANCE
 90-203.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  