| Notes |
| Date |
Text |
| 2015-06-19 08:26:04 | 1) SUBMIT MANUFACTURER SPECS. ON THE MAIN DRAINS BEING | | | USED. WPB AMEND. TO 2010 FBC SEC. 107.2.1.2ND REQUEST. | | | 2) SHOW THE DISTANCE BETWEEN THE TWO MAIN DRAINS.WPB | | | AMEND. TO 2010 FBC SEC. 107.2.1.2ND REQUEST. | | | 3) SUBMIT PUMP CURVE INFO.2ND REQUEST. | | | 4) SUBMIT SPECS. FOR THE PUMP, SKIMMER AND TABLET | | | FEEDER.2ND REQUEST. | | | 5) THE POTABLE WATER SUPPLY SHALL BE PROTECTED WITH A | | | RPZ BACKFLOW PREVENTION DEVICE PER THE CITY OF WPB | | | CROSS CONNECTION MANUAL. 2ND REQUEST. | | | 6) THE PLANS AND ISOMETRIC SHOW A 4" MAIN DRAIN BUT THE | | | FOUNTAIN CROSS SECTION SHOWS A 6" MAIN DRAIN. CLARIFY. | | | 2ND REQUEST. | | | 7) THE PLAN SHOWS 2" OVERFLOW TO ON-SITE STORM DRAIN. | | | CLARIFY "ON-SITE STORM DRAIN. THE OVERDLOW SHALL NOT | | | DISCHARGE TO THE STORMWATER SYSTEM PER CITY ORDINANCE | | | 90-203. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|