Plan Review Notes
Plan Review Notes For Permit 15040794
Permit Number 15040794
Review Stop E
Sequence Number 2
Notes
Date Text
2015-06-18 10:50:12THE SECOND REVIEW FAILED DUE TO FAILURE TO PROVIDE THE
 PREVIOUSLY REQUESTED ITEMS AS INDICATED BELOW FOR
 CLARITY:
 1. FBC- 107.3.5.3 ? ELECTRIC SERVICE RISER WITH WIRE
 SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE
 LOAD CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON
 FLOOR PLAN. WHICH WAS INITIALLY REQUESTED WITH
 REFERENCE TO NEC 215.5
 2. NEC 230.70 - YOU SHALL INDICATE THE LOCATION OF THE
 DISCONNECTING MEANS FOR THIS PANEL
 3. NEC 225.34(A) - THE DISCONNECT SHALL BE LABELED TO
 INDICATE LOAD SERVED.
 4. NEC 680.22 - THE CIRCULATING PUMPS SHALL BE
 PROTECTED WITH A GFI CIRCUIT.
  
 YOU CAN VIEW ANY OTHER COMMENTS BY SELECTING THE PLAN
 REVIEWS TAB AT: HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/
 PERMIT/PERM_STATUS.ASPX .
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
  