| Plan Review Notes For Permit 15040794 |
| Permit Number |
15040794 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-06-18 10:50:12 | THE SECOND REVIEW FAILED DUE TO FAILURE TO PROVIDE THE | | | PREVIOUSLY REQUESTED ITEMS AS INDICATED BELOW FOR | | | CLARITY: | | | 1. FBC- 107.3.5.3 ? ELECTRIC SERVICE RISER WITH WIRE | | | SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE | | | LOAD CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON | | | FLOOR PLAN. WHICH WAS INITIALLY REQUESTED WITH | | | REFERENCE TO NEC 215.5 | | | 2. NEC 230.70 - YOU SHALL INDICATE THE LOCATION OF THE | | | DISCONNECTING MEANS FOR THIS PANEL | | | 3. NEC 225.34(A) - THE DISCONNECT SHALL BE LABELED TO | | | INDICATE LOAD SERVED. | | | 4. NEC 680.22 - THE CIRCULATING PUMPS SHALL BE | | | PROTECTED WITH A GFI CIRCUIT. | | | | | | YOU CAN VIEW ANY OTHER COMMENTS BY SELECTING THE PLAN | | | REVIEWS TAB AT: HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/ | | | PERMIT/PERM_STATUS.ASPX . | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | | CONTACT ME DIRECTLY. | | | | | | THANK YOU, | | | |
|