| Notes |
| Date |
Text |
| 2015-06-08 05:13:06 | 1) SUBMIT MANUFACTURER SPECS. ON THE MAIN DRAINS BEING | | | USED. WPB AMEND. TO 2010 FBC SEC. 107.2.1. | | | 2) SHOW THE DISTANCE BETWEEN THE TWO MAIN DRAINS.WPB | | | AMEND. TO 2010 FBC SEC. 107.2.1. | | | 3) SUBMIT PUMP CURVE INFO. | | | 4) SUBMIT SPECS. FOR THE PUMP, SKIMMER AND TABLET | | | FEEDER. | | | 5) THE POTABLE WATER SUPPLY SHALL BE PROTECTED WITH A | | | RPZ BACKFLOW PREVENTION DEVICE PER THE CITY OF WPB | | | CROSS CONNECTION MANUAL. | | | 6) THE PLANS AND ISSOMETRIC SHOW A 4" MAIN DRAIN BUT | | | THE FOUNTAIN CROSS SECTION SHOWS A 6" MAIN DRAIN. | | | CLARIFY. | | | 7) THE PLAN SHOWS 2" OVERFLOW TO WASTE. CLARIFY | | | TERMINATION POINT. THE OVERDLOW SHALL NOT DISCHARGE TO | | | THE STORMWATER SYSTEM PER CITY ORDINANCE 90-203. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|