2015-05-04 11:46:0715040794
 600 OKEECHOBEE BLVD.
 COMMERCIAL FOUNTAIN
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS
  
 PROVIDE FEEDER DETAILS FOR THE NEW ELECTRICAL
 PANELBOARD FOR THE FOUNTAIN. NEC 215.5
  
 VERIFY THAT ALL FEEDERS FROM THE ELECTRICAL SERVICE
 SOURCE INCLUDE A FULL SIZE INSULATED COPPER EQUIPMENT
 GROUNDING CONDUCTOR SIZED IN ACCORDANCE WITH NEC
 250.22, 680.21, 680.25
  
 SHOW THE LOCATION AND SAFETY CLEARANCES REQUIRED FOR
 THE NEW PANEL BOARD SERVING THE FOUNTAIN EQUIPMENT. NEC
 110.26
  
  
 ROBERT LECKY
 ELECTRICAL PLANS REVIEW
  
  
  