| Plan Review Notes For Permit 15040783 |
| Permit Number |
15040783 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-05-20 09:33:23 | ELECTRICAL PROVISO: | | | BECAUSE THIS IS AN ADDITION TO AN EXISTING SYSTEM, IT | | | IS ASSUMED THAT ALL REQUIRED DEVICES SUBORDINATE TO | | | THIS INSTALLATION AND THE SURROUNDING AREAS THOUGH NOT | | | INDICATED ON THE DRAWINGS AS EXISTING ARE IN PLACE. ANY | | | MISSING DEVICES WILL HAVE TO BE ADDED FOR FINAL | | | INSPECTION AND INCLUDED IN AN AS-BUILT DRAWING WHICH IS | | | TO BE APPROVED BY THE CITY OF WEST PALM BEACH. | | | A RE-ACCEPTANCE TEST REPORT AS REQUIRED BY NFPA 72 | | | SECTION 14.4.2 SHALL BE PROVIDED FOR FIRE & ELECTRICAL | | | INSPECTORS AND INCLUDED IN THE SYSTEM LOG BOOK. | | | |
|