Plan Review Notes
Plan Review Notes For Permit 15040761
Permit Number 15040761
Review Stop E
Sequence Number 1
Notes
Date Text
2015-05-18 14:51:51APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN APPROVED
 PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION
 FEE(S).
  
 1) ALL NEW RECEPTACLE OUTLETS CUT INTO EXISTING FIRE
 RATED PARTITIONS SHALL BE PROTECTED IN COMPLIANCE WITH
 FBC 713.3.2
  
 2) THE CIRCUIT FOR THE INSTA-HOT IS IDENTIFIED ON THE
 FLOOR PLAN AS CIRCUIT H9 BUT ON THE PANEL SCHEDULE AS
 H11.
  