2015-04-27 09:27:50BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15040765
 MASTER: 15040757
 ADD: 6910 S. DIXIE HWY.
 CONT: MODERN ROOFING
 TEL: (954) 524-1322
 E-MAIL: ??????
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. APRIL 27/2015
 ACTION: DENIED
  
 1) THE ROOFING PERMIT WAS ACCOMPANYED WITH P. B. C.
 ROOFING FORM 100, WITHIN THE FORM IT LIST SYSTEM,
 APPLICANT WROTE AS PER RAS 150, THIS IS A PRESCRIPTIVE
 METHOD FOR BROWARD & MIAMI-DADE COUNTIES ONLY. THIS
 PROTION OF THE CODE WAS ADOPTED ONLY IN THOSE COUNTIES
 THAT ELECTED TO BE IN THE HIGH-VELOCITY HURRICANE
 ZONES. THE CITY OF WEST PALEM BEACH WILL ACCEPT
 MIAMI-DADE NOAS' BUT WE HAVE NOT ADOPTED THE
 HIGH-VELOCITY HURRICANE STANDARDS.
  
 FOR T THE FLAT ROOF PORTION OF THE ROOF. PLEASE PROVIDE
 THE PRODUCT APPROVAL TO BE INSTALLED. NOTE THE PRODUCT
 APPROVAL CAN EITHER BE A MIAMI-DADE NOA OR FL STATE
 APPROVAL. REVIEW THE PRODUCT APPROVAL, CIRCLE WHICH
 SUB-SYSTEM TO BE INSTALLED, PLEASE SEE LIMITATIONS AND
 IF ENHANCED FASTENING WILL BE REQUIRED IN ZONES 2 AND
 3. LIMITATIONS MAY REQUIRE THE DESIGN PROFESSIONAL TO
 COMLPY WITH RAS 117 IF A NOA. SEE FL. APPROVAL ALSO FOR
 ENHANCED FASTENING REQUIREMENTS.
  
 2) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE
 CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND
 DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS,
 FASTENING REQUIREMENTS, FLASHING REQUIREMENTS AND WIND
 RESISTANCE RATING THAT ARE REQUIRED TO BE INSTALLED.
 PRODUCT EVALUATION AND INSTALLATION SHALL INDICATE
 COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR THE
 SPECIFIC SITE OR A STATEMENT BY AN ARCHITECT OR
 ENGINEER FOR THE SPECIFIC SITE MUST BE SUBMITTED WITH
 THE CONSTRUCTION DOCUMENTS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]